- Do not leave dryer filters or the compres-

sor out in the open air.

- For welding use low melting point rods

with a 5% silver content, minimum.

- When welding and as long as the tubing

is hot, maintain a flow of dry nitrogen so
as to avoid internal rusting and scaling
that could cause contamination and ob-
struction.

- Do not use strippers on copper-copper

joints.

- Connection to the units should be carried

out by means of the flaring method.

Insulation of refrigerant tu-
bing

Due to the fact that the capillary tubing is in-
stalled in the outdoor unit, both the larger as
well as the smaller diameter tubes are in the
relative low pressure side of the system.
Consequently, to avoid condensed water
dripping on the floor, both tubes should be
insulated adequately. The thickness of same
should be at least 8 mm.

Emptying and dehydrating

Air does not act as a refrigerant since it can-
not be liquefied by the compressor. Any air
and humidity remaining in the cooling sys-
tem has undesirable effects, as indicated
below.
Consequently, they should be eliminated
completely.
- High pressure increases.

- Consumed power supply increases.

- Equipment performance decreases.

- Water contained in the air could freeze

and block the capillaries.

- Water can cause corrosion of certain parts

of the circuit, and deterioration of the com-
pressor.

Process
In each circuit:
1- Connect a vacuum pump and service

pressure gages.

2- Carry out a vacuum of up to at least

50 microns.

3- Detect leaks.

Refrigerant load

The refrigerant load is calculated for a
tubling length of 7.5m. See refrigerant load
table, in accordance with model and size.

Adjusting refrigerant load
For tubing lengths longer or shorter than
7.5 m., the nominal refrigerant load should
be increased or decreased by the grams
indicated in the following table, in accord-
ance with the increase or decrease in the
length of the liquid tubing.
Make sure the refrigerant load is correct by
measuring overheating. In normal summer
conditions, 5 °K is correct.

Detecting leaks

Once load is complete, replace the caps on
the charging valves and check for leaks.

Application of R-407-C refrige-
rant

Due to the characteristics of R-407-C
refrigerant, its evaporating, condensing
and discharge temperatures, its high
operating pressure in the units and the
specific requirements needed for efficient
operation (free from dampness and dirt), a
specially trained technical team with the
corresponding certification is required for
handling same.

GB

Wiring

In all cases, the established National regu-
lations
 should be followed. Each unit is sup-
plied with a control box to which the po-
wer supply will be connected by means of
a fused main switch or an automatic
switch.

Thermostat connection

For connecting thermostat to control board,
10 x 0.22 mm

screened communication

cable should be used.

Configuration of the electronic
board

For start-up after the accessories are in-
stalled, connect power supply to the unit. To
have the electronic board respond in accord-
ance with the accessories installed, press
the "test" button a few seconds, until the red
LED goes out.
The "test" button should be pressed only
when the board is under electric current. If
pressed and held without any current at the
board, and then the power supply is con-
nected, the microprocessor will lose its con-
figuration and the board assembly will have
to be replaced.

Scroll compressors, rotational
direction

The Scroll compressors, just like the fans,
operate correctly in only one rotational
direction. Upon starting the unit up, this
rotational direction should be checked. If it is
not correct:
- The compressor does not compress.
- It makes abnormal noise.
- The consumption of amps is low.
- It overheats.
The compressor should not be allowed to
operate under these conditions. In this case,
change the order of two of the three power
supply wires going to the compressor.

Refrigerating piping

R-407-C (Mixture of 3

refrigerants: HFC-32 + HFC-

125 + HFC-134a)

Standard compressor

P.O.E. oil

Charge in liquid phase

(by weight)

T° Evaporation with

displacement (7°C)

High vacuum 50 microns in 2 stages

Detection of difficult leaks

(requires detector

adapted to R-407-C)

Gas line diameter

Liquid line diameter

Model

5/8" (15.87 mm)

1/2" (12.7 mm)

7/8" (22 mm)

1

3

/

8

" (35 mm)

1

1

/

8

" (28.5 mm)

SCOC-076K  & 150K
SCOH-070K, 076K  & 150K

SCOC-090K, 180K
SCOH-090K, 120K, 180K

SCOC-240K
SCOH-300K

Summary of Contents for SCOH-070K

Page 1: ...Los productos se corresponden con los relacionados en el Directorio EUROVENT de Productos Certificados en el programa AC1 AC2 y AC3 Clima Roca York S L is participating in the EUROVENT Certification...

Page 2: ...2...

Page 3: ...n rales Dimens es gerais Dimensioni d ingombro Sllgemeine Abmessungen Algemene afmetingen Generelle dimensjoner Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 Fig 6 Fig 7 SCOC 076K SCOH 070K 076K 1069 147 144 1360 13...

Page 4: ...lgemeine Abmessungen Algemene afmetingen Generelle dimensjoner SCOC 090K SCOH 090K 120K SCOC 150K SCOH 150K Fig 10 mm 1444 148 146 1738 1526 30 37 324 996 139 1738 1485 111 142 24 36 327 395 36 327 39...

Page 5: ...rales Dimens es gerais Dimensioni d ingombro Sllgemeine Abmessungen Algemene afmetingen Generelle dimensjoner 101 148 66 2025 1641 30 37 389 1047 138 2239 2060 114 65 24 40 323 451 40 323 451 777 962...

Page 6: ...d Amount Nombre Quantidade Quantit Anzahl Aantal Antall Superficie Surface Surface Superf cie Superficie Oberfl che Oppervlak Overflate Dimensiones con embalaje Dimensions with packing Dimensions avec...

Page 7: ...vacuarse a trav s del desag e Debe preverse la eventualidad de una obs trucci n del desag e por elementos extra os polvo o suciedad Espacios libres Debe dejarse en la instalaci n de cada apa rato espa...

Page 8: ...que se indican en la tabla siguiente seg n se haya aumen tado o disminuido la longitud de la tuber a de l quido Verificar que la carga de refrigerante es correcta midiendo el sobrecalentamiento En con...

Page 9: ...8 15 87mm 170 20 SCOH 150K SICH 150B 9 4 x 2 2 1 2 12 7 mm 104 20 SCOH 180K SICH 180B 9 x 2 2 5 8 15 87mm 170 20 SCOH 240K SICH 240C 13 x 2 2 7 8 22 mm 347 20 SCOH 300K SICH 300B 16 x 2 2 7 8 22 mm 34...

Page 10: ...aci n son orientativos y deber n corregirse en base a las condiciones de la obra longitud entre unidades y la legislaci n vigente Notas 1 Curva K DIN VDE 0660 104 2 Basada en conductores de cobre Inte...

Page 11: ...eft in the installation of each unit for a Air intake and discharge of the outdoor unit b Connection of drain and electrical tub ing c Air ducts d Maintenance servicing e Power supply connection Air d...

Page 12: ...nd check for leaks Application of R 407 C refrige rant Due to the characteristics of R 407 C refrigerant its evaporating condensing and discharge temperatures its high operating pressure in the units...

Page 13: ...SCOH 076K SICH 070B 076B 8 7 1 1 2 12 7 mm 104 20 SCOH 090K SICH 090B 120B 13 8 1 5 8 15 87mm 170 20 SCOH 120K SICH 090B 120B 13 1 5 8 15 87mm 170 20 SCOH 150K SICH 150B 9 4 x 2 2 1 2 12 7 mm 104 20 S...

Page 14: ...re orientative and should be corrected in accordance with conditions at job site length between units and legislation in force Notes 1 K curve DIN VDE 0660 104 2 Based on copper conductors Electrical...

Page 15: ...il faudra vacuer travers un syst me de drai nage Il faudra aussi pr voir une ventuelle obs truction du tube de drainage par des l ments trangers tels que poussi re ou toute autre salet D gagements n c...

Page 16: ...ccourci V rifier si la charge de r frig rant est cor recte en mesurant la surchauffe Dans des conditions nominales d t 5 K est correct D tection des fuites Une fois la charge compl t e remettre les bo...

Page 17: ...K SICH 070B 076B 8 7 1 1 2 12 7 mm 104 20 SCOH 090K SICH 090B 120B 13 8 1 5 8 15 87mm 170 20 SCOH 120K SICH 090B 120B 13 1 5 8 15 87mm 170 20 SCOH 150K SICH 150B 9 4 x 2 2 1 2 12 7 mm 104 20 SCOH 180K...

Page 18: ...ominaleA Compresseur Ventilateur Compresseur Ventilateur Mod le D marrage Nominale D marrage Nominale mm2 Section c blage d alimentation 2 A Interrupteur automatique Courbe K 1 400 3 50 400 3 50 99 14...

Page 19: ...mentos estranhos ao p ou sujidade Espa os livres Na instala o de cada aparelho dever haver espa o livre para a Admiss o e descarga de ar da unidade exterior b Liga o dos tubos de desaguamento e el ctr...

Page 20: ...nte H que verificar se a carga de refrigerante a correcta ao medir o sobreaquecimento Em condi es nominais de Ver o 5 K o correcto Detec o de fugas Depois de completada a carga h que co locar tamp es...

Page 21: ...076K SICH 070B 076B 8 7 1 1 2 12 7 mm 104 20 SCOH 090K SICH 090B 120B 13 8 1 5 8 15 87mm 170 20 SCOH 120K SICH 090B 120B 13 1 5 8 15 87mm 170 20 SCOH 150K SICH 150B 9 4 x 2 2 1 2 12 7 mm 104 20 SCOH 1...

Page 22: ...icionar at a 10 C Ciclodefuncionamento Limitesdevoltagem Ciclodefuncionamento TemperaturaentradaarparaabateriaexteriorTS Limites de utiliza o 342 436 19 46 24 15 10 2 23 32 20 1 Alimenta oV ph Hz Cons...

Page 23: ...revedere l eventualit di un ostruzione del lo scarico ad opera di corpi estranei polve re o sporcizia Spazi liberi Nell installazione di ogni apparecchio si devono lasciare gli opportuni spazi liberi...

Page 24: ...di liquido Controllare che la carica di refrigerante sia quella adeguata misurandone il surriscal damento In condizioni normali estive il va lore corretto di 5 K Ricerca di eventuali perdite Una volta...

Page 25: ...SICH 070B 076B 8 7 1 1 2 12 7 mm 104 20 SCOH 090K SICH 090B 120B 13 8 1 5 8 15 87mm 170 20 SCOH 120K SICH 090B 120B 13 1 5 8 15 87mm 170 20 SCOH 150K SICH 150B 9 4 x 2 2 1 2 12 7 mm 104 20 SCOH 180K...

Page 26: ...tallazione alla distanza tra le unit ed alla legislazione vigente Note 1 Curva K DIN VDE 0660 104 2 Basata su conduttori di rame AlimentazioneV ph Hz ConsumonominaleA Compressore Ventilatore Compresso...

Page 27: ...er Au en batterie beim Betriebszyklus im Winter gro e Mengen Kondenswasser anfallen die entsprechend abgeleitet werden m ssen Zu ber cksichtigen ist dar ber hinaus auch die M glichkeit einer Verstopfu...

Page 28: ...nge F r Leitungen ber oder unter 7 5 Meter mu die K ltemittelmenge entsprechend angepa t werden Pro laufendem Meter um den die Leitung erweitert oder verk rzt wurde ist hier bei die in nachstehender T...

Page 29: ...7 mm 104 20 SCOC 180K SICH 180B 9 x 2 2 5 8 15 87mm 170 20 SCOH 070K SICH 070B 076B 9 2 1 2 12 7 mm 104 20 SCOH 076K SICH 070B 076B 8 7 1 1 2 12 7 mm 104 20 SCOH 090K SICH 090B 120B 13 8 1 5 8 15 87mm...

Page 30: ...ehen und m ssen vor Ort den gegebenenVerh ltnissen dem Abstand zwischen den verschiedenen Einheiten sowie den g ltigen gesetzlichen Auflagen angepa t werden Anm 1 Kurve K DIN VDE 0660 104 2 Bezogen au...

Page 31: ...te worden ge houden dat in de bedrijfscyclus winter de buitenbatterij een grote hoeveelheid water condenseert dat via de afvoer afgevoerd dient te worden Men dient rekening te houden met de mo gelijk...

Page 32: ...ling in gram zie on derstaande tabel verhoogd dan wel ver laagd te worden wanneer de vloeistofleiding verlengd of ingekort is Controleer of de koelmiddelvulling correct is door de verhitting te meten...

Page 33: ...H 076K SICH 070B 076B 8 7 1 1 2 12 7 mm 104 20 SCOH 090K SICH 090B 120B 13 8 1 5 8 15 87mm 170 20 SCOH 120K SICH 090B 120B 13 1 5 8 15 87mm 170 20 SCOH 150K SICH 150B 9 4 x 2 2 1 2 12 7 mm 104 20 SCOH...

Page 34: ...j Nominaal 400 V Verwarming Koeling Bedrijfscyclus Maximum C Minimum C Minimaal Maximaal Maximum C Minimum C Koeling Bedrijfscyclus Temperatuur bij luchtinlaat van buitenbatterij DB Verwarming Koeling...

Page 35: ...mer st v og smuss Frie avstander Ved installering av hvert apparat m det avsettes plass til a Inntak og utbl sing av luft fra utvendig enhet b Kobling av avl psr r og elektriske led ninger c Luftkanal...

Page 36: ...ventilene og unders ker om det finnes lekkasjer Bruk av kj lemiddel R 407 C P grunn av kj lemiddelet R 407 C s egenskaper fordampnings kondensasjons og utladetemperatur det h ye driftstrykket det har...

Page 37: ...K SICH 070B 076B 8 7 1 1 2 12 7 mm 104 20 SCOH 090K SICH 090B 120B 13 8 1 5 8 15 87mm 170 20 SCOH 120K SICH 090B 120B 13 1 5 8 15 87mm 170 20 SCOH 150K SICH 150B 9 4 x 2 2 1 2 12 7 mm 104 20 SCOH 180K...

Page 38: ...Anmerkninger TH V tt termometer TS T rrtermometer 1 Ved temperaturer under 20 vil kun den elektriske reserveresistansen v re tilkoblet opsjonell 2 Apparatet kan arbeide p en temperatur under 10 C i e...

Page 39: ...39...

Page 40: ...R C G nova 6 28004 Madrid EN292 1 EN292 2 EN563 EN294 EN953 EN378 EN60204 1 EN50081 2 EN50082 2 98 37 CEE 73 23 CEE 89 336 CEE 97 23 CEE CEDECLARATIONOFCONFORMITY SIGNED BY MANUFACTURER CLIMA ROCA YOR...

Reviews: