GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. Package units give you the flexibility and
choices you need in today’s market. These packaged cooling/
heating air conditioners are designed for outdoor installation.
Only utility and duct connections are required at the point of
installation. The single-stage gas fired heaters have stainless
steel tubular heat exchangers and spark to burner ignition.
They are available in natural gas with field conversion to
propane.

DESCRIPTION

Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heating units, designed for outdoor installation.
For SEER ratings, refer to technical literature. They shall have
built in, equal size, field convertible duct connections for supply/
return or horizontal supply/return. The units shall be factory
wired, piped, charged with R-410A Refrigerant and factory
tested prior to shipment. All unit wiring shall be both numbered
and color coded. All models shall be rated in accordance with
DOE and AHRI test procedures for both heating and cooling
operation. Units shall be CSA listed and classified to ANSI
Z21.47/CAN/ CSA 2.3 standards and UL 1995/CAN/CSA No.
236-M90 standards.

UNIT CABINET

Unit cabinet shall be constructed of G-90 galvanized, powder-
painted steel, certified at 1000 hours salt spray test per ASTM-
B117 standards. The unit top shall be a single piece design,
with drip edges and no-seam corners to provide optimum water
integrity. Unit shall have a rigidly mounted outdoor coil guard to
provide protection from objects and personnel after installation.
Indoor blower section shall be insulated with foil-faced or foam
insulation, fastened to prevent insulation from entering the air
stream. Cabinet panels shall be separate, easily removable for
servicing and maintenance. Unit shall be built on a formed,
design base pan, with embossments at critical points to add
strength and rigidity and to aid in minimizing sound. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, for truck access and proper
sealing on roof curb applications. Base rails shall be easily
removable, when required to lower unit height. Filters shall be
field installed, furnished and be accessible through a removable
access door, sealed airtight. Units vertical discharge and return
duct configuration shall be designed to fit between standard 24”
O.C. beams without modification to building structure, duct work
and base unit. Condensate pan shall be internally sloped and
conform to ASHRAE 62-89 self-draining standards, with 3/4”
NPT female ridged mount connection.

Indoor Blower Assembly - 

Fan shall be direct drive design.

Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently
lubricated for longer life and no maintenance. Fan assembly
shall be a slide-out design for easy removal and cleaning.
Indoor blower motors shall be equipped with a standard high
efficiency brushless DC motor (constant torque) also known as
a standard ECM motor.

Outdoor Fan Assembly -

 The outdoor fan shall be of the

direct-driven propeller type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
permanently lubricated bearings and internally protected
against overload conditions.

REFRIGERANT COMPONENTS
Compressors:

a. Shall be fully hermetic type, direct drive, internally pro-

tected with internal high-pressure relief and over tempera-
ture protection. The hermetic motor shall be suction gas
cooled and have a voltage range of +/- 10% of the unit
nameplate voltage.

b. Shall have internal isolation and sound muffling to mini-

mize vibration and noise, and be externally isolated on a
dedicated, independent mounting.

Coils:

a. Indoor coils shall have aluminum plate fins mechanically

bonded to seamless internally enhanced tin-coated cop-
per tubes with all joints brazed.

b. Indoor coil shall be of the direct expansion, draw through

design.

c. Outdoor coils shall have aluminum plate fins mechanically

bonded to seamless internally enhanced copper tubes
with all joints brazed.

d. Outdoor coil shall be draw through design.

Refrigerant Circuit and Refrigerant Safety Components 
shall include:

a. Thermal expansion devices (TXVs) shall be factory

mounted and provided.

b. Filter/strainer to eliminate any foreign matter.

Summary of Contents for PCG6B36

Page 1: ...gerant charge and component part numbers are verified via computers during assembly Vital run test statistics such as system pressure motor cur rents air velocity and temperature unit vibration and gas system safeties are monitored and recorded by the system to ensure unit performance Equal size side supply and return duct connections allow easy connection of ducts to match low crawl spaces withou...

Page 2: ...artment The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures All wiring internal to the unit is color number coded Protected Compressor The compressor is internally pro tected against high pressure and temperature This is accomplished by the simultaneous operation of scroll bypass and ...

Page 3: ...ation Level 1 first generation 4 Nominal Air Conditioning Cooling Capacity BTUx1000 24 24 000 BTU etc 9 Revision Level A original release B second release Examples PHG4B421002X1A is a dual fuel 14 SEER 3 1 2 ton large cabinet single stage heat 100 000 BTU gas heat 230 volt single phase low NOx model first generation first release COMPONENT LOCATION FAN MOTOR OUTDOOR FAN COIL GUARD PANEL OUTDOOR CO...

Page 4: ... Kit includes one supply and one return air rectangle to round duct adapter Adapters are preformed and designed to fit over current horizontal duct openings on the base unit Transition is from rectangle to 12 round for the 1AK0110 kit and from rectangle to 14 round for the 1AK0111 kit Rectangle to Round Downflow Adapter S1 1AK0108 S1 1AK0109 Kit includes one supply and one return air rectangle to ...

Page 5: ...easily removable when required to lower unit height Filters shall be field installed furnished and be accessible through a removable access door sealed airtight Units vertical discharge and return duct configuration shall be designed to fit between standard 24 O C beams without modification to building structure duct work and base unit Condensate pan shall be internally sloped and conform to ASHRA...

Page 6: ...48 PCG6B60 3 0 3 5 4 0 5 0 AHRI Cooling Performance Gross Capacity AHRI A point MBH 36 5 43 3 49 1 60 0 AHRI net capacity MBH 36 0 42 5 45 5 58 0 EER 12 5 12 5 12 0 12 0 SEER 16 0 16 0 16 0 16 0 Nominal CFM 1200 1400 1600 2000 System power KW 3 0 3 4 3 6 4 6 Refrigerant type R410A R410A R410A R410A Refrigerant charge lb oz 11 8 11 4 13 8 14 0 AHRI Gas Heat Performance Heating model 65 100 65 100 6...

Page 7: ...l CFM 3200 3200 3200 3200 Direct Drive Indoor Fan Data Fan Size Inch 11 x 10 11 x 10 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Centrifugal Motor HP each 1 2 3 4 3 4 3 4 1 RPM 1200 Max 1200 Max 1200 Max 1200 Max Frame size 48 48 48 48 Filters Filter Size B B B B Quantity Size Field supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable fil...

Page 8: ...7 6 18 1 15 4 16 6 11 0 18 7 19 4 17 7 18 5 11 7 K W 4 23 4 22 4 19 4 19 4 13 4 17 4 18 4 18 4 15 4 10 4 11 4 14 4 17 4 12 4 07 COOLING PERFORMANCE DATA 3 TON HIGH SPEED MODEL NO PCG6B36 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1000 1200 1400 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 38 5 41 0 40 0 43 2 46 6 41 2 42 8 41 7 45 6 4...

Page 9: ... 14 6 17 3 18 5 11 7 15 6 15 6 19 3 20 8 13 1 K W 2 45 2 45 2 42 2 44 2 42 2 46 2 46 2 44 2 45 2 43 2 47 2 47 2 46 2 45 2 44 COOLING PERFORMANCE DATA HIGH 3 5 TON HIGH SPEED MODEL NO PCG6B42 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1120 1320 1520 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 43 6 47 7 30 8 50 0 55 0 45 8 49 6 31 8 51...

Page 10: ...4 17 5 12 5 20 4 11 4 17 9 17 6 11 8 22 3 12 1 K W 3 98 4 10 3 98 3 91 3 89 3 99 4 05 4 00 3 92 3 93 4 00 4 01 4 02 3 93 3 97 COOLING PERFORMANCE DATA HIGH 4 TON HIGH SPEED MODEL NO PCG6B48 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1400 1600 1800 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 46 5 54 3 55 5 56 6 59 6 47 9 54 3 55 6 56 ...

Page 11: ... 24 3 27 5 24 6 25 9 18 4 25 1 26 7 25 2 27 5 19 6 K W 4 57 4 38 4 39 4 35 4 32 4 58 4 47 4 49 4 46 4 43 4 58 4 57 4 59 4 56 4 54 COOLING PERFORMANCE DATA 5 TON HIGH SPEED MODEL NO PCG6B60 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1600 1800 2000 IDDB 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80 IDWB 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 55 45 T C 59 2 68 9 66 5 71 8 77 1 61 3 70 6 67 6 73 5...

Page 12: ... installed on combustible materials made from wood or class A B or C roof covering materials only if factory base rails are left in place as shipped 1 NOTES INDOOR BLOWER SPECIFICATIONS Model Motor HP RPM EFF SF Frame 36065 1 2 Variable 0 8 1 0 48 36100 42065 42100 48065 48100 48125 3 4 Variable 0 8 1 0 48 60065 60100 60125 1 Variable 0 8 1 0 48 SOUND PERFORMANCE Model Tons Sound Rating1 dB A 1 Ra...

Page 13: ... NOTES 1 Minimum Circuit Ampacity 2 Maximum Over Current Protection per standard UL 1995 3 Fuse or HACR circuit breaker to be field installed X CENTER OF GRAVITY FRONT OF UNIT Y D C B A A0295 001 TG COMPRESSOR WEIGHTS DIMENSIONS Model Weight lbs Center of Gravity 4 Point Load Location lbs Shipping Operating X Y A B C D 36065 466 461 28 15 161 113 96 91 36100 473 468 28 15 163 114 101 90 42065 500 ...

Page 14: ...2 1352 1318 1276 1226 1168 1123 1067 1017 957 B 1251 1205 1157 1107 1051 987 938 884 824 761 C 1139 1087 1027 968 907 839 785 733 663 598 D 984 922 841 769 700 625 564 515 430 361 42065 High Cool A 1555 1518 1494 1459 1414 1360 1318 1261 1220 1162 B 1473 1435 1406 1368 1320 1264 1220 1164 1119 1060 C 1374 1333 1298 1255 1204 1145 1100 1044 993 933 D 1216 1168 1117 1064 1007 942 892 838 775 712 Low...

Page 15: ... 1851 1809 1781 1746 1707 1656 1609 1552 1518 1460 B 1689 1652 1630 1597 1556 1504 1461 1404 1368 1310 C 1614 1578 1554 1520 1477 1424 1382 1324 1286 1228 D 1374 1333 1298 1255 1204 1145 1100 1044 993 933 Low Cool A 1473 1435 1406 1368 1320 1264 1220 1164 1119 1060 B 1374 1333 1298 1255 1204 1145 1100 1044 993 933 C 1322 1278 1238 1191 1138 1077 1030 975 920 859 D 1286 1241 1197 1149 1095 1032 984...

Page 16: ...8 1516 1469 1423 1375 1329 1280 1232 1181 1135 C 1453 1406 1355 1305 1255 1207 1153 1100 1047 997 D 1410 1361 1307 1255 1204 1155 1100 1044 992 938 High Heat A 2259 2221 2183 2142 2099 2060 2015 1975 1931 1882 B 2093 2059 2023 1977 1938 1896 1852 1805 1760 1712 C 1908 1872 1835 1792 1753 1709 1665 1619 1566 1522 D 1760 1726 1685 1641 1598 1552 1510 1463 1413 1370 Low Heat A 2259 2221 2183 2142 209...

Page 17: ...0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08 1800 0 08 0 04 0 09 1900 0 09 0 05 0 10 2000 0 09 0 05 0 11 048 4 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05 1400 0 05 0 03 0 05 1500 0 06 0 04 0 06 1600 0 07 0 04 0 07 1700 0 07 0 04 0 08 1800 0 08 0 04 0 09 1900 0 09 0 05 0 10 2000 0 09 0 05 0 11 060 5 0 1100 0 02 0 02 0 04 1200 0 03 0 02 0 04 1300 0 04 0 02 0 05...

Page 18: ...REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A0324 001 UNIT TYPICAL SLAB ON GROUND INSTALLATION A0325 001 SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOFF VAVLE CONDENSATE DRAIN ...

Page 19: ...oducts 19 UNIT TYPICAL ROOF CURB INSTALLATION SUPPLY AIR DUCT TO POWER SUPPLY RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH CONTROL WIRING TO INDOOR THERMOSTAT TO GAS SUPPLY LINE MANUAL GAS SHUTOFF VAVLE ROOF CURB ROOF CONDENSATE DRAIN A0326 001 ...

Page 20: ... change without notice Published in U S A 5291596 YTG E 1117 Copyright 2017 by Johnson Controls Inc All rights reserved Supersedes 5291596 YTG D 1017 York International Corp 5005 York Drive Norman OK 73069 NOTES ...

Reviews: