Johnson Controls Unitary Products
GAS HEATING SECTION (If Equipped)
Heat exchanger and exhaust system shall be constructed of
corrosion-resistant materials and shall be designed with
induced draft combustion with post purge logic and redundant
main gas valve. The heat exchanger shall be of the tubular
type, constructed of stainless steel for corrosion resistance and
allowing minimum mixed air entering temperature of 40 ºF.
Burners shall be of the in-shot type, constructed of
aluminumized steel. All gas piping shall enter the unit cabinet at
a single location through either the side or bottom, without any
field modifications. An integrated control board shall provide
timed control of indoor fan functioning and burner ignition.
Heating section shall be provided with the following minimum
protection:
a. Primary high-temperature limit switch.
b. Induced draft pressure switch.
c. Flame roll out switch(es) (manual reset).
d. Flame proving controls.
All gas heat models will meet the California requirement for
emissions of less than 40 nanograms per Joule (California
requirement on single phase models only).
PHYSICAL DATA
NOMINAL TONNAGE
MODELS
PCG6B36
PCG6B42
PCG6B48
PCG6B60
3.0
3.5
4.0
5.0
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
36.5
43.3
49.1
60.0
AHRI net capacity (MBH)
36.0
42.5
45.5
58.0
EER
12.5
12.5
12.0
12.0
SEER
16.0
16.0
16.0
16.0
Nominal CFM
1200
1400
1600
2000
System power (KW)
3.0
3.4
3.6
4.6
Refrigerant type
R410A
R410A
R410A
R410A
Refrigerant charge (lb-oz)
11-8
11-4
13-8
14-0
AHRI Gas Heat Performance
Heating model
65
100
65
100
65
100
125
65
100
125
Heat input - High Fire (KBtu)
65
100
65
100
65
100
125
65
100
125
Heat output - High Fire (KBtu)
52
81
52
81
52
81
101
52
81
101
Heat input - Low Fire (KBtu)
43
65
43
65
43
65
82
43
65
82
Heat output - Low Fire (KBtu)
34
53
34
53
34
53
66
34
53
66
AFUE %
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
No. burners
2
3
2
3
2
3
4
2
3
4
No. stages
2
2
2
2
2
2
2
2
2
2
Temperature Rise Range - High Fire (°
F)
40-70
40-70
40-70
40-70
Temperature Rise Range - Low Fire (°
F)
25-55
25-55
25-55
25-55
Max. Static Pressure w.c.
0.5
0.5
0.5
0.5
Max. Outlet Air Temp. (°
F)
180
180
180
180
Gas piping connection (in.)
1/2
1/2
1/2
1/2
Dimensions (inches)
Length
51-1/4
51-1/4
51-1/4
51-1/4
Width
45-3/4
45-3/4
45-3/4
45-3/4
Height
49
49
53
55
Compressor
Type
Scroll
Scroll
Scroll
Scroll
Stages
2
2
2
2
Outdoor Coil Data
Face area (Sq. Ft.)
19.5
19.5
23.8
25.9
Rows
2
2
2
2
Fins per inch
22
22
22
22
Tube diameter
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Continued on next page.