5291596-YTG-E-1117
16
Johnson Controls Unitary Products
60100
High Cool
A 2149
2114
2077
2030
1989
1948
1905
1859
1816
1768
B 2013
1977
1941
1898
1860
1816
1772
1726
1677
1630
C 1936
1900
1864
1822
1783
1739
1695
1649
1597
1551
D 1719
1685
1642
1600
1555
1508
1465
1418
1372
1327
Low Cool
A 1629
1591
1546
1502
1455
1409
1362
1315
1266
1220
B 1558
1516
1469
1423
1375
1329
1280
1232
1181
1135
C 1453
1406
1355
1305
1255
1207
1153
1100
1047
997
D 1410
1361
1307
1255
1204
1155
1100
1044
992
938
High Heat
A 1739
1705
1664
1620
1577
1530
1487
1441
1393
1348
B 1558
1516
1469
1423
1375
1329
1280
1232
1181
1135
C 1410
1361
1307
1255
1204
1155
1100
1044
992
938
D 1323
1270
1213
1156
1104
1052
993
933
880
821
Low Heat
A 1594
1553
1507
1462
1415
1369
1321
1274
1223
1178
B 1323
1270
1213
1156
1104
1052
993
933
880
821
C 1181
1118
1049
980
913
857
795
743
696
640
D 1025
950
868
788
713
654
591
505
458
415
60125
High Cool
A 2149
2114
2077
2030
1989
1948
1905
1859
1816
1768
B 2013
1977
1941
1898
1860
1816
1772
1726
1677
1630
C 1936
1900
1864
1822
1783
1739
1695
1649
1597
1551
D 1719
1685
1642
1600
1555
1508
1465
1418
1372
1327
Low Cool
A 1629
1591
1546
1502
1455
1409
1362
1315
1266
1220
B 1558
1516
1469
1423
1375
1329
1280
1232
1181
1135
C 1453
1406
1355
1305
1255
1207
1153
1100
1047
997
D 1410
1361
1307
1255
1204
1155
1100
1044
992
938
High Heat
A 2259
2221
2183
2142
2099
2060
2015
1975
1931
1882
B 2093
2059
2023
1977
1938
1896
1852
1805
1760
1712
C 1908
1872
1835
1792
1753
1709
1665
1619
1566
1522
D 1760
1726
1685
1641
1598
1552
1510
1463
1413
1370
Low Heat
A 2259
2221
2183
2142
2099
2060
2015
1975
1931
1882
B 1965
1929
1893
1851
1813
1769
1724
1678
1628
1580
C 1701
1666
1623
1580
1535
1488
1445
1397
1351
1305
D 1683
1648
1604
1560
1515
1468
1424
1377
1330
1284
NOTES:
1. Airflow tested with dry coil conditions, without air filters, at 230 volts
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
5. Minimal variations in airflow performance data results from using downflow duct applications. Data above may be used in those cases.
6. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION (Continued)
Model
Jumper Position
External Static Pressure (Inches WC)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM
SCFM