ELECTRICAL DATA
Model
Voltage
Compressor
OD Fan
Motor
Supply
Blower Motor
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
36065
208/230-3-60
11.6
73.0
18.1
1.7
3.8
20.0
30
36100
208/230-3-60
11.6
73.0
18.1
1.7
5.4
21.6
30
42065, 42100
208/230-3-60
14.2
88.0
22.1
1.7
5.4
24.9
35
48065, 48100, 48125
208/230-3-60
14.0
83.1
21.9
1.7
5.4
24.6
35
60065, 60100, 60125
208/230-3-60
16.2
110.0
25.3
1.7
7.0
29.0
40
NOTES:
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker to be field installed.
X
CENTER OF
GRAVITY
FRONT
OF UNIT
Y
"D"
"C"
"B"
"A"
A0295-001-TG
COMPRESSOR
WEIGHTS & DIMENSIONS
Model
Weight (lbs.)
Center of Gravity
4 Point Load Location (lbs.)
Shipping
Operating
X
Y
A
B
C
D
36065
466
461
28
15
161
113
96
91
36100
473
468
28
15
163
114
101
90
42065
500
495
28
15
175
123
104
93
42100
502
497
28
15
176
124
101
96
48065
520
515
28
15
189
116
93
117
48100
528
523
28
15
169
139
115
100
48125
533
528
28
15
164
145
124
95
60065
537
532
29
15
174
142
124
92
60100
541
536
28
15
177
140
117
102
60125
548
543
27
15
151
167
141
84