5291596-YTG-E-1117
Johnson Controls Unitary Products
17
ADDITIONAL STATIC RESISTANCE
Size (Tons)
CFM
Wet Indoor Coil
Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter pressure drop based on standard filter media tested at velocities not to
exceed 300 ft/min.
Filter/Frame Kit
036 (3.0)
700
0.01
0.00
0.04
800
0.02
0.01
0.06
900
0.03
0.01
0.08
1000
0.04
0.01
0.10
1100
0.05
0.01
0.13
1200
0.06
0.02
0.16
1300
0.07
0.03
0.17
1400
0.08
0.04
0.18
042 (3.5)
1100
0.02
0.02
0.04
1200
0.03
0.02
0.04
1300
0.04
0.02
0.05
1400
0.05
0.03
0.05
1500
0.06
0.04
0.06
1600
0.07
0.04
0.07
1700
0.07
0.04
0.08
1800
0.08
0.04
0.09
1900
0.09
0.05
0.10
2000
0.09
0.05
0.11
048 (4.0)
1100
0.02
0.02
0.04
1200
0.03
0.02
0.04
1300
0.04
0.02
0.05
1400
0.05
0.03
0.05
1500
0.06
0.04
0.06
1600
0.07
0.04
0.07
1700
0.07
0.04
0.08
1800
0.08
0.04
0.09
1900
0.09
0.05
0.10
2000
0.09
0.05
0.11
060 (5.0)
1100
0.02
0.02
0.04
1200
0.03
0.02
0.04
1300
0.04
0.02
0.05
1400
0.05
0.03
0.05
1500
0.06
0.04
0.06
1600
0.07
0.04
0.07
1700
0.07
0.04
0.08
1800
0.08
0.04
0.09
1900
0.09
0.05
0.10
2000
0.09
0.05
0.11
NOTES:
BOTTOM DUCT DIMENSIONS (Inches)
Model
A
B
C
D
E
F
36, 42, 48, 60
14
13.5
5
3.5
47.5
42
REAR DUCT DIMENSIONS (Inches)
Model
A
B
36, 42, 48, 60
13.6
14
$
'
´
&
$
%
$
6833/<
$,5'8&7
5(7851
$,5'8&7
)
(
´
9,(:/22.,1*83
$7%277202)81,7
+2/(
´
ZLWK´JURPPHW
RSHQLQJIRUJDVSLSH
+2/(
´
IRUKLJK
YROWDJH
+2/(
´IRU
ORZYROWDJH
$
%
$
$
6833/<
$,5'8&7
5(7851
$,5'8&7
127(6HH)LJXUHWLWOHG³8QLW'LPHQVLRQV´IRUVLGHKROHVL]HVRI
HOHFWULFDODQGJDVOLQHV