background image

035-17480-000 Rev. A (800)

Unitary Products Group

13

VENTING MULTIPLE UNITS

Each unit must have its own intake/vent piping and termina-
tion. Do not use common pipes for combustion air or venting.
The vent terminals must be located as shown in Figure 14
and Figure 15.

PIPING ASSEMBLY

The final assembly procedure for the vent/combustion air pip-
ing is as follows:

1.

Cut piping to the proper length, beginning at the furnace.

2.

Deburr the piping inside and outside.

3.

Chamfer the outer edges of the piping.

4.

Dry-fit the entire vent/combustion air piping assembly.

FIGURE 11 :

Horizontal Termination Raised Configura-
tion For Additional Clearance

FIGURE 12 :

Horizontal Termination Configuration With
Horizontal Extension

VENT

OVERHANG

COMBUSTION AIR

(ELBOW PARALLEL TO WALL)

12" SEPARATION BETWEEN

BOTTOM OF COMBUSTION AIR

AND BOTTOM OF VENT

MAINTAIN 12" CLEARANCE ABOVE

HIGHEST ANTICIPATED SNOW LEVEL

OR GRADE, WHICHEVER IS GREATER

12" MINIMUM

90°

VENT

OVERHANG

COMBUSTION AIR

12" SEPARATION BETWEEN

BOTTOM OF COMBUSTION AIR

AND BOTTOM OF VENT

MAINTAIN 12" CLEARANCE ABOVE

HIGHEST ANTICIPATED SNOW LEVEL

OR GRADE, WHICHEVER IS GREATER

12" MINIMUM

90°

18" MAXIMUM

FIGURE 13 :

Vertical Termination

FIGURE 14 :

Double Sidewall Termination

FIGURE 15 :

Double Rooftop Termination

MAINTAIN 12" MINIMUM

CLEARANCE ABOVE HIGHEST

ANTICIPATED SNOW LEVEL.

MAXIMUM OF 24" ABOVE ROOF

COMBUSTION AIR

VENT

12" VERTICAL SEPARATION

BETWEEN COMBUSTION

AIR AND VENT

VENT

COMBUSTION AIR

2"

6"

Summary of Contents for P*XU/G9D-UP

Page 1: ...TART UP AND ADJUSTMENTS 20 ACCESSORY CONNECTIONS 24 FURNACE ACCESSORIES 25 FILTER PERFORMANCE 26 OPERATION AND MAINTENANCE 26 TROUBLESHOOTING 30 FURNACE CONTROL DIAGNOSTICS 30 WIRING DIAGRAM UPFLOW MO...

Page 2: ...THREE TWO PIPE SYSTEM USING COMBUSTION AIR FROM A VENTILATED ATTIC SPACE 18 HORIZONTAL VENT APPLICATIONS 18 CONDENSATE PIPING 19 SAFETY CONTROLS 19 START UP AND ADJUSTMENTS 20 IGNITION SYSTEM SEQUENCE...

Page 3: ...ransit There are no shipping or spacer brackets which need to be removed NOTES CAUTIONS WARNINGS The installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended...

Page 4: ...size as determined using the appropriate tables in Appendix G of the above codes SPECIFIC UNIT INFORMATION LIMITATIONS LOCATION This furnace should be installed in accordance with all national and lo...

Page 5: ...leaning Eighteen 18 inches at the side where access is required for passage to the front when servicing or for inspection or replacement of flue vent connections 8 Where it will not interfere with the...

Page 6: ...ust comply with the National Electrical Code NFPA 70 latest edition For altitudes above 2 000 ft reduce capacity 4 for each 1 000 ft above sea level Refer to Form 650 78 N1 1V Wire size based on coppe...

Page 7: ...ls NOTE In order to achieve the airflow indicated in the table it is recommended those applications over 1800 CFM use return air from two sides one side and the bottom or bottom only For single return...

Page 8: ...cation outside the utility room or basement For further details consult Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1 or 2 Installation Cod...

Page 9: ...for 63 F 35 C rise wire when installed in accordance with instructions Refer the rating plate or Physi cal and Rating Data Tables in these instructions for specific furnace electrical data Provide a p...

Page 10: ...mostat to the terminal board on the ignition module Connect Class 2 control wiring for single stage thermostat or for two stage thermostat Refer to Figure 7 for single stage and Fig ure 8 for two sta...

Page 11: ...e observed Long radius elbows are required for all units 1 Long radius elbows are required for all units 2 Elbows are assumed to be 90 degrees Two 45 degree elbows count as one 90 degree elbow 3 Elbow...

Page 12: ...e grade and anticipated snow depth 1 ft Above grade when adjacent to public walkway 7 ft From electric gas meters regulators and relief equipment min horizontal distance 4 ft Does not apply to multipl...

Page 13: ...ional Clearance FIGURE 12 Horizontal Termination Configuration With Horizontal Extension VENT OVERHANG COMBUSTION AIR ELBOW PARALLEL TO WALL 12 SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM O...

Page 14: ...fined space is an area with less than 50 cubic feet per 1000 Btu hr input rating for all appliances installed in that area The following must be considered to obtain proper air for combustion and vent...

Page 15: ...all be permitted to be waived where special engineering approved by the authority having jurisdiction provides an adequate supply of air for combus tion ventilation and dilution of flue gases Combusti...

Page 16: ...nted vertical terminals may be field fabricated Standard PVC SRD fittings may be used Terminal configuration must comply as detailed in this section When selecting the locations for vent termination t...

Page 17: ...ater tight seal 7 Support the vent piping such that it is angled 1 4 per lin ear foot so that condensate will flow back towards the furnace Piping should be supported with pipe hangers to prevent sagg...

Page 18: ...Table 5 on page 16 Follow all notes installation procedures and required materials in the METHOD TWO ONE PIPE SYSTEM on page 14 to install the vent pipe from the unit to the outdoors VENT TERMINATION...

Page 19: ...quiva lent pipe be field installed as drain pipe The condensate piping may be tied together with the air conditioning con densate drain if the air conditioning condensate drain line is trapped upstrea...

Page 20: ...furnace the gas piping may be full of air In order to purge this air it is recommended that the ground union be loosened until the odor of gas is detected When gas is detected immediately retighten th...

Page 21: ...more accurate input rate adjustment To calculate a meter correction factor use the following formula Using the information from above calculate the gas input rat ing by multiplying the number of cubi...

Page 22: ...djustment 1 Turn off all electrical power to the system at main fuse or circuit breaker 2 Attach a manometer to the outlet pressure tap of the valve 3 Turn on power and energize main and redundant P M...

Page 23: ...crease the rise All direct drive blowers have multi speed motors The blower motor speed taps are located in the control box in the blower compartment Refer to Figure 28 and the unit wiring label to ch...

Page 24: ...ion of the circulating blower NOTE EAC and HUM power leads are provided in the junction box for easier installation FIGURE 27 Upflow Models P XU G9D UP Reading Gas Pressure GAS VALVE U TUBE MANOMETER...

Page 25: ...5 1075 1060 1045 1030 1000 960 910 830 755 LOW 805 795 785 770 755 730 700 655 615 565 80 75 1600 C HIGH 1940 1905 1870 1815 1760 1700 1620 1555 1460 1305 MED 1400 1390 1380 1370 1355 1320 1285 1255 1...

Page 26: ...urnace with 2 return openings and operating on high speed blower it is found that total sys tem static is 0 58 w c To determine the system airflow com plete the following steps 1 Obtain the airflow va...

Page 27: ...035 17480 000 Rev A 800 Unitary Products Group 27 FIGURE 29 Sequence Timing For 50a51 243 Control...

Page 28: ...eriod the gas valve is de energized the ignitor is turned off and the 50A51 control goes into the retry sequence The retry sequence provides a 120 second wait with inducer inter purge following an uns...

Page 29: ...l the filter simply reverse this procedure Lubrication Blower motors in these furnaces are permanently lubricated and do not require periodic oiling BLOWER CARE Even with good filters properly in plac...

Page 30: ...valves in the gas line to the furnace must be open 3 Make sure all wiring connections are secure 4 Review the sequence of operation Start the system by setting the thermostat above the room temperatur...

Page 31: ...used by a number of problems blocked vent or chimney faulty inducer cracked pressure switch hose 7 FLASH This fault code indicates that flame could not be established This no light condition occurred...

Page 32: ...NACE RELAY IGNITER GV GRD DOOR SWITCH N O SW ELEMENTARY DIAGRAM POWER SUPPLY 120 1 60 SEE NOTE 1 GRD DS C NO LS1 C 1LP COM 120V 24V SEC PRI 1T 40VA VENTOR MOTOR HSI NOTES LEGEND DOT DELAY ON TIMER FUS...

Reviews: