![background image](http://html.mh-extra.com/html/york/millennium-ycul0016sc/millennium-ycul0016sc_assembly-installation-operation-and-maintenance_947525068.webp)
YORK INTERNATIONAL
68
DIMENSIONS - YCUL0026SC (METRIC)
Installation
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated
performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated
below, resulting in unpredictable airflow patterns and possible diminished performance. YORK’s unit controls will optimize
operation without nuisance high-pressure safety cutouts; however, the system designer must consider potential performance
degradation. Access to the unit control center assumes the unit is no higher than on spring isolators. Recommended mini-
mum clearances: Side to wall – 2m; rear to wall – 2m; control panel to end wall – 1.2m; top – no obstructions allowed;
distance between adjacent units – 3m. No more than one adjacent wall may be higher than the unit.
All dimensions are in mm unless specified otherwise.
LD05723
LD05724
VIEW B-B
CONTROL ENTRY
(4) 13 CONDUIT K.O.'S
POWER ENTRY
(2) 51, 38 CONDUIT K.O.'S
(4) 13 CONDUIT K.O.'S
44 TYP.
35
149
44 TYP.
51
114
114
165
89
LIQUID
STOP VALVE
LIQUID CONN.
22
410
564
VIEW A-A
1308
297
SUCT. CONN. 41
SUCTION
STOP VALVE
Summary of Contents for MILLENNIUM YCUL0016SC
Page 35: ...YORK INTERNATIONAL FORM 150 63 NM1 35 This page is intentionally left blank 1 ...
Page 151: ...YORK INTERNATIONAL FORM 150 63 NM1 151 This page is intentionally left blank 5 ...
Page 155: ...YORK INTERNATIONAL FORM 150 63 NM1 155 This page is intentionally left blank 5 ...
Page 159: ...YORK INTERNATIONAL FORM 150 63 NM1 159 This page is intentionally left blank 5 ...
Page 163: ...YORK INTERNATIONAL FORM 150 63 NM1 163 This page is intentionally left blank 5 ...
Page 170: ...YORK INTERNATIONAL 170 ...