YORK INTERNATIONAL
26
ELECTRICAL DATA
SINGLE POINT POWER (Standard or Optional Disconnect or Breakers)
Installation
See Notes on page 24.
SINGLE POINT FIELD SUPPLIED WIRING
MODEL
INCOMING
YCUL
VOLT
HZ
MCA
1
MIN N/F
D.E. FUSE
CKT. BKR.
5
WIRE
DISC SW
2
MIN
3
MAX
4
MIN
MAX
RANGE
6
0016SC
200
60
75
100
90
100
90
100
# 4 - # 1
230
60
70
100
80
90
80
90
# 4 - # 1
380
60
42
60
45
50
45
50
# 8 - # 4
460
60
34
60
40
40
40
40
# 10 - # 6
575
60
27
30
30
35
30
35
# 10 - # 6
0026SC
200
60
100
150
110
125
110
125
# 2 - 1/0
230
60
93
100
110
125
110
125
# 2 - 1/0
380
60
52
60
60
60
60
60
# 6 - # 2
460
60
45
60
50
60
50
60
# 8 - # 4
575
60
36
60
40
45
40
45
# 8 - # 4
200
60
127
150
150
175
150
175
# 1 - 2/0
0030SC
230
60
118
150
150
150
150
150
# 1 - 2/0
380
60
76
100
90
100
90
100
# 4 - # 1
460
60
57
60
70
70
70
70
# 6 - # 2
575
60
46
60
50
60
50
60
# 8 - # 4
0036SC
200
60
140
150
175
175
175
175
1/0 - 3/0
230
60
130
150
150
175
150
175
1/0 - 3/0
380
60
75
100
90
100
90
100
# 4 - # 1
460
60
62
100
70
80
70
80
# 6 - # 2
575
60
50
60
60
60
60
60
# 6 - # 2
0040SC
200
60
183
200
200
225
200
225
3/0 - 250
230
60
170
200
200
200
200
200
2/0 - 4/0
380
60
103
150
110
125
110
125
# 2 - 1/0
460
60
81
100
90
100
90
100
# 4 - # 1
575
60
65
100
70
80
70
80
# 4 - # 1
Summary of Contents for MILLENNIUM YCUL0016SC
Page 35: ...YORK INTERNATIONAL FORM 150 63 NM1 35 This page is intentionally left blank 1 ...
Page 151: ...YORK INTERNATIONAL FORM 150 63 NM1 151 This page is intentionally left blank 5 ...
Page 155: ...YORK INTERNATIONAL FORM 150 63 NM1 155 This page is intentionally left blank 5 ...
Page 159: ...YORK INTERNATIONAL FORM 150 63 NM1 159 This page is intentionally left blank 5 ...
Page 163: ...YORK INTERNATIONAL FORM 150 63 NM1 163 This page is intentionally left blank 5 ...
Page 170: ...YORK INTERNATIONAL 170 ...