YORK INTERNATIONAL
136
TABLE 31 – SUCTION TEMP. SENSOR
TEMPERATURE/VOLTAGE/
RESISTANCE CORRELATION
TEMP °F
VOLTAGE
RESISTANCE
TEMP °C
0
1.71
25619
-18
2
1.78
24046
-17
4
1.85
22580
-16
6
1.93
21214
-14
8
2.00
19939
-13
10
2.07
18749
-12
12
2.15
17637
-11
14
2.22
16599
-10
16
2.30
15629
-9
18
2.37
14721
-8
20
2.45
13872
-7
22
2.52
13077
-6
24
2.59
12333
-4
26
2.67
11636
-3
28
2.74
10982
-2
30
2.81
10370
-1
32
2.88
9795
0
34
2.95
9256
1
36
3.02
8750
2
38
3.08
8276
3
40
3.15
7830
4
42
3.21
7411
6
44
3.27
7017
7
46
3.33
6647
8
48
3.39
6298
9
50
3.45
5970
10
52
3.51
5661
11
54
3.56
5370
12
56
3.61
5096
13
58
3.67
4837
14
60
3.72
4593
16
62
3.76
4363
17
64
3.81
4145
18
66
3.86
3941
19
68
3.90
3747
20
70
3.94
3564
21
72
3.98
3392
22
74
4.02
3228
23
76
4.06
3074
24
78
4.10
2928
26
80
4.13
2790
27
Control Service and Troubleshooting
Suction Temperature Sensor – System 1
J5-7 = +5 VDC regulated supply to sensor.
J5-12 = VDC input signal to the microboard. See
Table 31 for voltage readings that corre-
spond to specific suction temperatures.
J5-1 = Drain (shield connection = 0 VDC)
Suction Temperature Sensor – System 2
J5-8 = +5 VDC regulated supply to sensor.
J5-13 = VDC input signal to the microboard. See
Table 31 for voltage readings that corre-
spond to specific suction temperatures.
J5-2 = Drain (shield connection = 0 VDC)
Summary of Contents for MILLENNIUM YCUL0016SC
Page 35: ...YORK INTERNATIONAL FORM 150 63 NM1 35 This page is intentionally left blank 1 ...
Page 151: ...YORK INTERNATIONAL FORM 150 63 NM1 151 This page is intentionally left blank 5 ...
Page 155: ...YORK INTERNATIONAL FORM 150 63 NM1 155 This page is intentionally left blank 5 ...
Page 159: ...YORK INTERNATIONAL FORM 150 63 NM1 159 This page is intentionally left blank 5 ...
Page 163: ...YORK INTERNATIONAL FORM 150 63 NM1 163 This page is intentionally left blank 5 ...
Page 170: ...YORK INTERNATIONAL 170 ...