TABLE 7 – MICROPANEL POWER SUPPLY
ELECTRICAL DATA
1
OVER CURRENT PROTECTION,
UNIT VOLTAGE
UNIT VOLTAGE
CONTROL POWER
MCA
SEE NOTE B
NF DISC Sw
NOTE A
MIN
MAX
MODELS w/o
CONTROL TRANS
115-1-60/50
15A
10A
15A
30 A / 240V
-17
200-1-60
15A
10A
15A
30 A / 240V
-28
230-1-60
15A
10A
15A
30 A / 240V
MODELS w/
-40
380-1-60
15A
10A
15A
30 A / 480V
CONTROL TRANS
-46
460-1-60
15A
10A
15A
30 A / 480V
-58
575-1-60
15A
10A
15A
30 A / 600V
A. Minimum #14 AWG, 75
°
C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
LEGEND:
Factory Supplied
Supplied by Others
It is possible that multiple sources of power can be supplying the unit power panel. To pre-
vent serious injury or death, the technician should verify that no lethal voltages are present
inside the panel after disconnecting power, prior to working on the equipment.
Summary of Contents for MILLENNIUM YCUL0016SC
Page 35: ...YORK INTERNATIONAL FORM 150 63 NM1 35 This page is intentionally left blank 1 ...
Page 151: ...YORK INTERNATIONAL FORM 150 63 NM1 151 This page is intentionally left blank 5 ...
Page 155: ...YORK INTERNATIONAL FORM 150 63 NM1 155 This page is intentionally left blank 5 ...
Page 159: ...YORK INTERNATIONAL FORM 150 63 NM1 159 This page is intentionally left blank 5 ...
Page 163: ...YORK INTERNATIONAL FORM 150 63 NM1 163 This page is intentionally left blank 5 ...
Page 170: ...YORK INTERNATIONAL 170 ...