YORK INTERNATIONAL
FORM 150.63-NM1
147
TABLE 39 – ISN OPERATIONAL AND FAULT CODES
P56/58
OPERATIONAL CODE
P57/59
FAULT CODE
0
NO ABNORMAL CONDITION
0
NO FAULT
1
UNIT SWITCH OFF
1
VAC UNDERVOLTAGE
2
SYSTEM SWITCH OFF
2
LOW AMBIENT TEMPERATURE
3
LOCK-OUT
3
HIGH AMBIENT TEMPERATURE
4
UNIT FAULT
4
LOW LEAVING CHILLED LIQUID TEMP
5
SYSTEM FAULT
5
HIGH DISCHARGE PRESSURE
6
REMOTE SHUTDOWN
6
HIGH DIFFERENTIAL OIL PRESSURE
7
DAILY SCHEDULE SHUTDOWN
7
LOW SUCTION PRESSURE
8
NO RUN PERMISSIVE
8
HIGH MOTOR CURRENT
9
NO COOL LOAD
9
LLSV NOT ON
10
ANTI-COINCIDENCE TIMER ACTIVE
10
LOW BATTERY WARNING
11
ANTI-RECYCLE TIMER ACTIVE
11
HIGH OIL TEMPERATURE
12
MANUAL OVERRIDE
12
HIGH DISCHARGE TEMPERATURE
13
SUCTION LIMITING
13
IMPROPER PHASE ROTATION
14
DISCHARGE LIMITING
14
LOW MOTOR CURRENT /MP / HPCO
15
CURRENT LIMITING
15
MOTOR CURRENT UNBALANCED
16
LOAD LIMITING
16
LOW DIFFERENTIAL OIL PRESSURE
17
COMPRESSOR(S) RUNNING
17
GROUND FAULT
18
18
MP /HPCO
19
19
LOW EVAPORATOR TEMPERATURE
20
20
INCORRECT REFRIGERANT
PROGRAMMED
21
21
POWER FAILURE, MANUAL RESET
REQUIRED
22
22
I/O BOARD FAILURE
23
23
OIL TEMP INHIBIT (LOW OIL TEMP)
4
Summary of Contents for MILLENNIUM YCUL0016SC
Page 35: ...YORK INTERNATIONAL FORM 150 63 NM1 35 This page is intentionally left blank 1 ...
Page 151: ...YORK INTERNATIONAL FORM 150 63 NM1 151 This page is intentionally left blank 5 ...
Page 155: ...YORK INTERNATIONAL FORM 150 63 NM1 155 This page is intentionally left blank 5 ...
Page 159: ...YORK INTERNATIONAL FORM 150 63 NM1 159 This page is intentionally left blank 5 ...
Page 163: ...YORK INTERNATIONAL FORM 150 63 NM1 163 This page is intentionally left blank 5 ...
Page 170: ...YORK INTERNATIONAL 170 ...