YORK INTERNATIONAL
SETPOINT KEYS
GENERAL
The microprocessor utilizes leaving chilled liquid control
to maintain chilled liquid temperature within the pro-
grammed CONTROL RANGE (CR). Regulating leaving
chilled liquid temperature within the CR is accomplished
through capacity control of the compressor’s slide valve.
A series of load and unload pulses are sent to the com-
pressor slide valve to maintain LWT within a desired
range. Attention is also provided by the micro to maxi-
mize efficiency and minimize compressor cycling. The
control algorithm in the micro combines control zones
and internal timers to maintain chilled liquid temperatures
and minimize cycling of the two compressors. This
method of control is suitable for both water and brine
cooling. Control setpoints (CONTROL RANGE) are pro-
grammed into the panel to establish the desired range of
leaving chilled operating temperatures. A description of
the operation and programming follows.
PROGRAMMING CHILLED LIQUID TEMP / RANGE
Chilled Liquid/Temp Range
When the CHILLED LIQUID TEMP / RANGE key is
pressed, one of the following messages will be displayed
for 3 seconds:
This message will inform the user that the chiller is se-
lected to be controlled by a LOCAL (Control Panel)
Setpoint control or REMOTE (FAX 4500, Remote PWM
Signal, or Remote Control Center) Setpoint control.
Selection is made on the S1 Dip Switch on the Micropro-
cessor Board (Page 80). Normally, unless a FAX 4500,
Remote PWM Signal or Remote Control Center is con-
nected to the Micropanel, the Local Mode will be se-
lected.
The display will then scroll to a second message which
will display the desired CONTROL RANGE (CR) and the
“TARGET” temperature.
The CONTROL RANGE (CR) is the programmed varia-
tion in leaving chilled liquid temperature which is accept-
able to the user for the system application. The example
CHILLED LIQUID/
TEMP RANGE
L O C A L
W A T E R
T E M P
C O N T R O L
R E M O T E
W A T E R
T E M P
C O N T R O L
C R
=
4 2 . 0
T O
4 6 . 0
° F
T A R G E T
=
4 4 . 0
° F
FIG. 27 – SETPOINT KEYS
28164A
SETPOINT
KEYS
Summary of Contents for Millennium YCAS 316
Page 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Page 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Page 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Page 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Page 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Page 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Page 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Page 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Page 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...