FORM 201.10-NM1
111
YORK INTERNATIONAL
An example of the Under Voltage Safety display mes-
sage is shown below:
Flow Switch
The microprocessor monitors the closure of the flow
switch to assure that water flow is present in the evapo-
rator which prevents freeze-ups. The flow switch “dry”
contacts are connected between terminals 13 & 14 (Fig.
19). If the flow switch opens, the chiller will shut down
and the following STATUS message will be displayed:
Closing of the flow switch, when flow is present, will
cause the message to disappear and auto-start to occur.
CAUTION: NEVER BYPASS A FLOW SWITCH. THIS
WILL CAUSE DAMAGE TO THE CHILLER
AND VOID ANY WARRANTIES.
Print-out On Fault Shutdown
If an optional printer is installed, the micro will automati-
cally send the contents of the HISTORY Buffer #1 to the
printer anytime a fault shutdown occurs. This will allow
record keeping of individual faults, even though they do
not cause a lock-out of the system. This information may
be useful to identify developing problems and trouble-
shooting.
The NO RUN PERM fault messages will not be stored in
the History Buffer and will not cause an auto print-out.
NOTE: Due to extreme operating conditions or sys-
tems where control deficiencies are present,
occasional faults may occur with the associ-
ated printout. This may be normal and ex-
pected. Do not become alarmed.
An example of this print-out is shown in Fig. 30.
C H I L L E R
F A U L T :
V A C
U N D E R
V O L T A G E
S Y S
1
N O
R U N
P E R M
S Y S
2
N O
R U N
P E R M
FIG. 30 – AUTOMATIC FAULT PRINT-OUT
YORK INTERNATIONAL CORPORATION
MILLENNIUM SCREW CHILLER
ISN OPTION ENABLED
SOFTWARE VERSION W.04F.02.500.02
SAFETY SHUTDOWN NUMBER 1
SHUTDOWN @11:07PM 01 JAN 96
CHILLER FAULT:
VAC UNDER VOLTAGE SHUTDOWN
RETURN WATER TEMP
49.1 DEGF
LEAVING WATER TEMP
49.3 DEGF
LOW WATER CUTOUT
36.0 DEGF
COOLING RANGE
42.0 TO 44.0 DEGF
TARGET TEMP
43.0 DEGF
AMBIENT AIR TEMP
70.2 DEGF
LOW AMBIENT CUTOUT
25.0 DEGF
LOW PRESSURE CUTOUT
44 PSIG
LEAD SYSTEM
SYS 2
LOCAL REMOTE SETTING:
LOCAL
SYSTEM 1 DATA
COMPRESSOR STATUS
OFF
RUN TIME
0- 0- 0- 0 D-H-M-S
AVERAGE MTR
65 %FLA
PHASE L1 MTR
66 %FLA
PHASE L2 MTR
65 %FLA
PHASE L3 MTR
65 %FLA
DIFF OIL PRESSURE
0 PSID
SUCTION PRESSURE
72 PSIG
SATURATED SUCTION
42.6 DEGF
SUCTION TEMP
49.0 DEGF
SUPERHEAT
6.4 DEGF
DISCHARGE PRESSURE
214 PSIG
SATURATED DISCHARGE
106.2 DEGF
DISCHARGE TEMP
128.1 DEGF
OIL TEMP
131.2 DEGF
LIQUID INJECTION VALVE
OFF
FORWARD FANS
OFF
REVERSE FANS
OFF
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
RUN TIME
0- 0-42- 9 D-H-M-S
AVERAGE MTR
65 %FLA
PHASE L1 MTR
65 %FLA
PHASE L2 MTR
65 %FLA
PHASE L3 MTR
65 %FLA
DIFF OIL PRESSURE
4 PSID
SUCTION PRESSURE
62 PSIG
SATURATED SUCTION
35.8 DEGF
SUCTION TEMP
47.3 DEGF
SUPERHEAT
11.5 DEGF
DISCHARGE PRESSURE
215 PSIG
SATURATED DISCHARGE
106.4 DEGF
DISCHARGE TEMP
134.6 DEGF
OIL TEMP
85.2 DEGF
LIQUID INJECTION VALVE
OFF
FORWARD FANS
OFF
REVERSE FANS
OFF
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
Summary of Contents for Millennium YCAS 316
Page 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Page 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Page 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Page 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Page 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Page 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Page 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Page 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Page 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...