FORM 201.10-NM1
103
YORK INTERNATIONAL
NOTE: It will be required to program a value for each
system.
The allowable range of DESIGN COND TEMP. is 100 -
140°F (37.7-60°C) with the default set for 125°F (51.7°C).
The DESIGN SYSTEM COND TEMP. is password pro-
tected under the PROGRAM key. The displays will ap-
pear as follows:
Program the design temperature for the respective sys-
tem and press ENTER. Repeat for the other system. This
value is not password protected and can be programmed
anytime the PROGRAM key is pressed.
The LAG COMPRESSOR START POINT % is program-
mable in the Program mode. By selecting a LAG COM-
PRESSOR START %, the user is actually selecting the
% slide valve at which the lead compressor is allowed to
load, before the lag compressor is brought on. This % is
programmable from 40 - 99%.
NOTE: This is in contrast to Scheme 1 where LAG
COMPRESSOR START % relates to % FLA.
The micro will start the lead compressor whenever the
chilled liquid temperature is above the High Limit of the
Control Range (CR) and the 3 minute “Start Timer” has
timed out. The 3 minute “Start Timer” is the minimum
amount of time that the compressor must remain off af-
ter a cycling shutdown (Anti-Recycle Timer Timed Out)
or after power is first applied. Once started, the micro
will pulse the slide valve to load the lead compressor to
bring the chilled liquid temperature within the NEUTRAL
ZONE.
If temperature is not brought down to within the “Neutral
Zone”, the lag compressor will be brought on by the mi-
cro after the lead compressor loads up to the programmed
LAG COMPRESSOR START POINT % as determined
and programmed by the user.
If due to system conditions, the lead compressor does
not reach the programmed %, even though the lead com-
pressor may be fully loaded, the lag compressor will start
regardless of the programmed Start % after 5 minutes of
operation. This will occur whenever the lead compressor
cannot bring the LWT to within 2.0°F of the high end of
the CONTROL RANGE (CR). Once the lag compressor
is started, equalized loading and unloading of the two
compressors will occur based on slide valve %.
The 5 minute default for lag compressor start assures
that the lag compressor will start and load in situations
where error is introduced into the micro calculation for
computing slide valve %. These situations may occur
due to tolerances in discharge pressure transducers,
ambients, dirt on coils, subcooling, superheat, etc.
As mentioned above, after the lead compressor starts
and loads up to the programmed 40 - 99%, if tempera-
ture is still above the CONTROL RANGE (CR), the lag
compressor will come on. It will then be brought up to a
TABLE 5 – CHILLER SYS 1 AND SYS 2 MOTOR CURRENT = 100% FLA
MODEL
200 VOLTS (-17)
230 VOLTS (-28)
460 VOLTS (-46)
575 VOLTS (-58)
YCAS
ENGR. DATA
SYS 1 FLA
SYS 2 FLA SYS 1 FLA
SYS 2 FLA
SYS 1 FLA
SYS 2 FLA
SYS 1 FLA
SYS 2 FLA
140
6A2A2KN6A
338
338
294
294
147
147
118
118
160
6M4M4KN6A
406
406
354
354
176
176
141
141
170
6F5M5NN6A
484
484
421
421
210
210
169
169
180
6F5F5NN6A
484
484
421
421
210
210
169
169
190
6H6F5NN6A
598
484
522
421
259
210
207
169
216
6P7H6NN6A
—
—
—
—
320
259
254
207
236
6P7P7NN6A
—
—
—
—
320
320
254
254
246
6S7S7NN6A
—
—
—
—
320
320
254
254
216x
10H5H5NN6A
—
—
—
—
210
210
169
169
236x
10P6H6NN6A
—
—
—
—
259
259
207
207
266x
10S7S7NN6A
—
—
—
—
320
320
254
254
S Y S T E M
1
C O N D
T E M P
1 1 8 . 0 ° F
=
1 0 0
% L O A D
TABLE 6 – CHILLER SYS 1 AND SYS 2 DESIGN
CONDENSING TEMP (CTP)
MODEL
FOR ALL VOLTAGES
YCAS
ENGR. DATA
SYS 1 CTP
SYS 2 CTP
140
6A2A2KN6A
116.1°F
116.1°F
160
6M4M4KN6A
118.3°F
118.3°F
170
6F5M5NN6A
121.3°F
118.5°F
180
6F5F5NN6A
121.4°F
121.4°F
190
6H6F5NN6A
124.3°F
121.4°F
216
6P6H5NN6A
128.8°F
124.4°F
236
6P7H6NN6A
128.8°F
128.8°F
246
6P7P7NN6A
130.1°F
130.1°F
216x
10H5H5NN6A
115.4°F
115.4°F
236x
10P6H6NN6A
118.6°F
115.3°F
266x
10S7S7NN6A
119.6°F
119.6°F
Summary of Contents for Millennium YCAS 316
Page 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Page 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Page 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Page 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Page 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Page 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Page 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Page 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Page 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...