This message informs the operator that the micro senses
the outdoor ambient temperature is below 40°F and is
commanding the Evaporator Heater to turn on. Once
turned on, the heater will turn off at 45°F.
This message displays the accumulated Run Time on
SYS 1 since the last start.
This time is recorded in Days (D), Hours (H), Minutes
(M), and Seconds (S).
This message informs the operator that the SYS 1 Liq-
uid Line Solenoid is “OFF” (De-energized/Closed) or “ON”
(Energized/Open).
This message informs the operator that the micro is or is
not activating the liquid injection valve for SYS 1 for oil
cooling.
This message informs the operator of the number of for-
ward running pairs of condenser fans on SYS 1.
This message informs the operator whether the pair of
reversing condenser fans are running on SYS 1.
This message displays the accumulated Run Time on
SYS 2 since the last start.
This time is recorded in Days (D), Hours (H), Minutes
(M), and Seconds (S).
This message informs the operator that the SYS 2 Liq-
uid Line Solenoid is “OFF” (De-energized/Closed) or “ON”
(Energized/Open).
This message informs the operator that the micro is or is
not activating the liquid injection valve for SYS 2 for oil
cooling.
This message informs the operator of the number of for-
ward running pairs of condenser fans on SYS 2.
This message informs the operator whether the pair of
reversing fans are running on SYS 2.
History
The HISTORY key also allows the user to scroll through
the SAFETY SHUTDOWN display information relating
to the last 9 Safety Shutdowns which occurred. Informa-
tion contained in the micro’s SAFETY SHUTDOWN buff-
ers is very important when attempting to troubleshoot a
system problem. This data reflects system conditions at
the instant the fault occurred.
Information is stored in the SAFETY SHUTDOWN buff-
ers on every fault regardless of whether the fault caused
a Lockout to occur. The stored information is also not
affected by power failures (long term internal battery back-
up is built into the printed circuit board) or manual reset-
ting of a fault lock-out.
When the HISTORY key is pressed, the following mes-
sage will appear:
The operator must select which of the last three SAFETY
SHUTDOWN’s is desired. When deciding this, keep in
mind that SAFETY SHUTDOWN No. 1 is always the most
recent fault. As new fault information is stored, it is as-
signed as No. 1, No. 1 is assigned to No. 2, No. 2 is
assigned to No. 3, up to No. 9, and information stored
previously as No. 9 is discarded.
To select a SAFETY SHUTDOWN, simply press a “1”,
“2”, “3”, etc. key and press ENTER. Repetitively press-
ing the ENTER key will allow the operator to scroll through
the information available in the SAFETY SHUTDOWN
buffer.
E V A P O R A T O R
H E A T E R
S T A T U S
O F F
S Y S
1
R U N
T I M E
0 -
3 - 4 8 - 1 7
D - H - M - S
S Y S
1
L I Q U I D
L I N E
S O L E N O I D
S T A T U S
O N
S Y S
1
L I Q U I D
I N J E C T I O N
V A L V E
O N
S Y S
1
F O R W A R D
F A N S
S T A T U S
2
S Y S
1
R E V E R S E
F A N
S T A T U S
O F F
S Y S
2
R U N
T I M E
1 - 1 2 -
6 -
5
D - H - M - S
S Y S
2
L I Q U I D
L I N E
S O L E N O I D
S T A T U S
O N
S Y S
2
L I Q U I D
I N J E C T I O N
V A L V E
O F F
S Y S
2
F O R W A R D
F A N S
S T A T U S
O F F
S Y S
2
R E V E R S E
F A N
S T A T U S
O F F
HISTORY
D I S P L A Y
S A F E T Y
S H U T -
D O W N
N O . 1
( 1
T O
9 )
Summary of Contents for Millennium YCAS 316
Page 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Page 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Page 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Page 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Page 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Page 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Page 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Page 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Page 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...