FORM 201.10-NM1
81
YORK INTERNATIONAL
SWITCH 3
OPEN:
“LOCAL” mode allows an ISN or an RCC (Remote Control
Center) option panel to receive chiller data from the chiller
through the RS-485 port, but not change programmable
setpoint values remotely.
CLOSED:
“REMOTE” mode allows an ISN or an RCC (Remote
Control Center) option panel to receive chiller data from
the chiller through the RS-485 port. This mode will also
allow loading, unloading, shutdown, Leaving Water
Setpoint Reset, Current Limit Setpoint, and Lag Start
Setpoint from an ISN or RCC. If communications is lost
to the ISN or RCC, the micro will run the chiller on the
micro panel programmed values.
SWITCH 4
OPEN:
This switch is presently disabled. In the future, it will allow
selection of control from either thermal expansion valves
or electronic expansion valves.
CLOSED:
This switch is presently disabled. In the future, it will allow
selection of control from either thermal expansion valves
or electronic expansion valves.
SWITCH 5
OPEN:
Display messages will show units of measure in English
units (°F, PSI, etc.).
CLOSED:
Display messages will show units of measure in Scientific
International (Metric) units (°C, BAR, etc.)
SWITCH 6
OPEN:
This mode MUST be selected for chillers with Across-
the-line starters where only one contactor per compressor
is present in the power panel.
CLOSED:
This MUST be selected for chillers with Wye-Delta
starters where three contactors and wire wound power
resistors are present for each compressor in the power
panel.
L O C A L
C O N T R O L
M O D E
E N G L I S H
U N I T S
R E A D O U T
R E M O T E
C O N T R O L
M O D E
S I
U N I T S
R E A D O U T
T H E R M A L
E X P A N S I O N
V A L V E S
A C R O S S - T H E - L I N E
M O T O R
S T A R T I N G
T H E R M A L
E X P A N S I O N
V A L V E S
W Y E
D E L T A
M O T O R
S T A R T I N G
Summary of Contents for Millennium YCAS 316
Page 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Page 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Page 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Page 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Page 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Page 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Page 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Page 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Page 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...