FORM 201.10-NM1
95
YORK INTERNATIONAL
To program SYSTEM 2 COND TEMP, access the
password protected values as previously described. Key
in the value for the specific model number from Table 3
and press the ENTER key. The new value will be entered
into memory and the display will advance to the next
programmable option.
NOTE: Proper operation is dependent on proper
programming of this value.
Shown below is an example of this display:
COMMUNICATIONS MODE
COMMUNICATIONS MODE allows the operator to select
communications with a (1) ISN System or (2) an RCC
(Remote Control Center Option). To program the
COMMUNICATIONS MODE, key in the corresponding
number and press the ENTER key. The programmed
mode will be entered into memory and the display will
advance to the next programmable value. This is not
password protected and can be programmed anytime the
PROGRAM key is pressed.
LOAD SHARE BASED ON?
Selection of the LOAD SHARE BASED ON ? determines
whether loading/unloading (load sharing based on % FLA
or % slide valve). Generally, each should operate
satisfactory in most applications. The default method
utilizes % FLA and is simpler and requires less
programming. It is also less affected by ambient and
system conditions.
To select a method of load sharing, program a “1” for SV%
(slide value %) or a “2” for % FLA (motor current) and press
ENTER. The mode of control will be entered into memory
and the next programmable value will appear. This
selection is not password protected and can be
programmed at any time under the PROGRAM key.
Additional details regarding selection of this program
option are detailed starting on page 88.
ECONOMIZER VALVE ON POINT
(15-Ton TXV Liquid Supply Solenoid)
The Economizer Valve Solenoid On/Off points are
programmable by the user. At low load, the 15-ton TXV
solenoid is shut off to prevent feeding excessive liquid to
the compressor. As load rises, the 15-ton TXV solenoid
valve is energized, providing additional subcooling
needed for efficiency and additional motor cooling.
The recommended settings assume that compressor
start points are controlled by % FLA. Under these
conditions, the recommended ON Point is 50%.
To program the ECONOMIZER VALVE ON POINT,
access the password protected values described
previously. Key in the value and press “ENTER” key. The
new value will be entered into memory and the display will
advance to the next programmable value.
ECONOMIZER VALVE OFF POINT
(15-Ton TXV Liquid Supply Solenoid)
The Economizer Valve Solenoid On/Off points are
programmable by the user. At low load, the 15-ton TXV
solenoid is shut off to prevent feeding excessive liquid to
the compressor. As load rises, the 15-ton TXV solenoid
valve is energized, providing additional subcooling
needed for efficiency and additional motor cooling.
The recommended settings assume that compressor
start points are controlled by % FLA. Under these
conditions, the recommended OFF Point is 40%.
To program the ECONOMIZER VALVE OFF POINT,
access the password protected values described
S Y S T E M
2
C O N D
T E M P
1 1 9 . 0
° F
=
1 0 0 %
L O A D
C O M M U N I C A T I O N S
M O D E
1
=
I S N,
2
=
R C C ,
2
L O A D
S H A R E
B A S E D
O N ?
1
=
S V % ,
2
=
% F L A
2
E C O N O M I Z E R
V A L V E
O N
P O I N T
5 0 %
E C O N O M I Z E R
V A L V E
O F F
4 0 %
TABLE 3 – CHILLER SYS 1 AND SYS 2 DESIGN
CONDENSING TEMP (CTP)
MODEL
FOR ALL VOLTAGES
YCAS
ENGR. DATA
SYS 1 CTP
SYS 2 CTP
140
6A2A2KN6A
116.1°F
116.1°F
160
6M4M4KN6A
118.3°F
118.3°F
170
6F5M5NN6A
121.3°F
118.5°F
180
6F5F5NN6A
121.4°F
121.4°F
190
6H6F5NN6A
124.3°F
121.4°F
216
6P6H5NN6A
128.8°F
124.4°F
236
6P7H6NN6A
128.8°F
128.8°F
246
6P7P7NN6A
130.1°F
130.1°F
216x
10H5H5NN6A
115.4°F
115.4°F
236x
10P6H6NN6A
118.6°F
115.3°F
266x
10S7S7NN6A
119.6°F
119.6°F
Summary of Contents for Millennium YCAS 316
Page 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Page 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Page 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Page 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Page 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Page 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Page 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Page 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Page 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...