![York Millennium YCAS 216X Installation Operation & Maintenance Download Page 142](http://html1.mh-extra.com/html/york/millennium-ycas-216x/millennium-ycas-216x_installation-operation-and-maintenance_912654142.webp)
142
YORK INTERNATIONAL
PROBLEM
CAUSE
SOLUTION
LOW COMPRESSOR OIL
1. Low oil charge.
1. Oil level should be
LEVEL
visible in either sight
glass at all times. Add
YORK “E” (R-22) oil if
necessary.
“HIGH OIL DIFFERENTIAL
1. Oil filter is dirty.
1. Change oil filter.
PRESSURE” FAULT
2. Faulty oil or discharge
2. Check / replace
pressure transducers or
transducers or repair
wiring.
wiring.
“HIGH AMBIENT TEMP”
1. High ambient cut-out
1. Re-program cut-out.
FAULT
is set too low.
Auto restart will occur after
2. Temperature sensed
2. Verify displayed ambient
a drop in temperature.
incorrectly by thermistor.
temp. is or - 15°F
of a thermometer placed
next to the OAT sensor.
3. Fans rotating backwards.
3. Air flow from forward fans
must be up. Correct fan
rotation.
4. Air flow to unit restricted
4. Check recommended
or is being recirculated.
installation clearances.
“LOW AMBIENT TEMP”
1. Temperature of outside air
1. No problem exists.
FAULT
is below cut-out.
Cut-out = 25°F for standard
2. Temperature sensed
2. Verify displayed ambient
ambient operation.
incorrectly by thermistor.
temperature is or -
15°F of a thermometer
A Low Ambient Kit must be
placed next to the
be installed for operation
OAT sensor.
below 25°F.
3. Low ambient cut-out set
3. Adjust as necessary.
too high.
Summary of Contents for Millennium YCAS 216X
Page 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Page 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Page 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Page 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Page 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Page 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Page 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Page 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Page 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...