132
YORK INTERNATIONAL
YCAS 216X - 266X FAN CONTROL STRATEGY
The high efficiency chiller is equipped with 12 condenser
fans; 6 per system. Fan control from discharge pressure
is standard. Fan start/stop pressures are programmable
in the PROGRAM Mode (page 93) under the FAN CON-
TROL DISCHARGE PRESSURE SETPOINT and FAN
ON/OFF PRESS DIFF displays. Ambient temperature
has no effect on fan cycling.
When discharge pressure reaches the programmed
setpoint, the first trio of fans on a respective system
starts. After the first trio of fans are brought on in the
reverse direction, discharge pressure must rise an addi-
tional 20 PSIG above the setpoint before a second trio of
fans will be brought on in the forward direction. When this
trio of fans starts, the reversing fans will turn off. If dis-
charge pressures rises 40 PSIG above the setpoint, a
second trio of fans will start in the forward direction. This
is the same trio of fans that originally ran in the reverse
direction. The first trio of forward fans will also continue
to run.
The point at which each trio of fans cycles off is also
programmable. This is accomplished in the PROGRAM
Mode when the FAN ON/OFF PRESS DIFF display ap-
pears. The programmable “differential” establishes the
pressure at which each trio of fans turn off. The “differen-
tial” is the amount the discharge pressure must drop be-
low the pressure at which the fan turned on.
Locations of the fans and a table showing the operation
is shown in Fig. 41.
FAN
FAN RELAY
PRESSURE
ON
OFF
1, 2 & 9 REV
9M, 10M & 21 M
SETPOINT
SETPOINT – DIFF.
(SYS 1)
OR
5, 6 & 10 REV 15M, 16M & 22M
SETPOINT
SETPOINT – DIFF.
(SYS 2)
3, 4 & 11 FOR
6M, 8M & 19M
SETPOINT (SE 20 PSIG)
(SYS 1)
+ 20 PSIG
– DIFF
OR
7, 8 & 12 FOR 12M, 14M & 20M
SETPOINT (SE 20 PSIG)
(SYS 2)
+ 20 PSIG
– DIFF
1, 2 & 9 FOR
5M, 7M & 17M
SETPOINT (SE 40 PSIG)
(SYS 1)
+ 40 PSIG
– DIFF
OR
5, 6 & 10 FOR 11M, 13M & 18M
SETPOINT (SE 40 PSIG)
(SYS 2)
+ 40 PSIG
– DIFF
FIG. 41 – YCAS 216X - 266X FAN LOCATION / OPERATION
LD01268
Summary of Contents for Millennium YCAS 216X
Page 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Page 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Page 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Page 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Page 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Page 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Page 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Page 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Page 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...