![York Millennium YCAS 216X Installation Operation & Maintenance Download Page 12](http://html1.mh-extra.com/html/york/millennium-ycas-216x/millennium-ycas-216x_installation-operation-and-maintenance_912654012.webp)
12
YORK INTERNATIONAL
YCAS 140-246 DIMENSIONS
(SI)
NOTES:
1. Clearances - Recommended YORK clearances for peak performance, reliable operation and maintenance:
Side to wall 2438 mm*; Rear to wall 2438 mm; Control Panel End to wall 1524 mm*; Over the top - No obstructions allowed; Distance
between adjacent units 3658 mm, (Walls should be no higher than the unit.)
*No more than one high wall can be higher than the top of the unit. The area within the clearances shown above and area under the unit
must be kept clear of all obstructions or clutter that would impede air flow to the unit. In installations where winter operation is intended
and snow accumulations are expected, additional unit height must be provided to insure air flow.
NOTE: Reduced clearances may be used due to jobsite restrictions or competitive recommendations. The unit will unload to prevent the
condenser pressure and motor current from exceeding the maximum limits and will continue to operate without nuisance high pressure
or motor current cutouts even though the air flow will be restricted at these conditions.
2. Cooler liquid connection sizes (inlet and outlet) 8" victaulic for all models.
3. Dimensions are in mm.
4. Spring isolators (OPTIONAL) will increase overall height of unit.
5. Modules have 28.6 mm of space between to facilitate maintenance.
LD01441(R)
LD01443
Summary of Contents for Millennium YCAS 216X
Page 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Page 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Page 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Page 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Page 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Page 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Page 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Page 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Page 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Page 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...