YORK INTERNATIONAL
85
FORM 150.62-NM2
LOW AMBIENT CONDENSER FAN CONTROL
For unit operation below 25°F (-3.9°C) a low ambient kit
is required. The kit consists of a discharge pressure
transducer(s) and reversing contactors.
With the low ambient kit installed and the unit programmed
for low ambient operation, the condenser fans will oper-
ate as shown in Tables 38 and 39.
TABLE 38
– LOW AMBIENT CONDENSER FAN CONTROL – AMBIENT TEMPERATURE AND DISCHARGE
PRESSURE CONTROL
FAN STAGE
ON
OFF
1 - 1 FAN REV
OAT>25° F (-3.9°C)
OAT < 20° F (-6.7°C)
OR
AND
DP > ctrl_press
DP < ctrl_press - diff_press
2 - 1 FAN FWD
OAT>45°F (7.2°C)
OAT < 40°F (-4.40°C)
OR
AND
DP > ctrl_press + 20 PSIG (1.38 Bars)
DP < ctrl_press - diff 20 PSIG (1.38 Bars)
3 - 2 FANS FWD
OAT > 65°F (18.3°C)
OAT < 60°F (15.6°C)
OR
AND
DP > ctrl 40 PSIG (2.76 Bars)
DP < ctrl_press - diff 40 PSIG (2.76 Bars)
Again, notice that condenser fan operation can be pro-
grammed for either “temperature and discharge pressure
control,” or “discharge pressure control only” as described
under Condenser Fan Control.
The fan control on-pressure (ctrl_press) and the fan
differencial off-pressure (diff_press) are programmable
under the PROGRAM key.
TABLE 39
– LOW AMBIENT CONDENSER FAN CONTROL – DISCHARGE PRESSURE CONTROL
FAN STAGE
ON
OFF
1 - 1 FAN REV
DP > ctrl_press
DP < ctrl_press - diff_press
2 - 1 FAN FWD
DP > ctrl_press + 20 PSIG (1.38 Bars)
DP < ctrl_press - diff 20 PSIG (1.38 Bars)
3 - 2 FANS FWD
DP > ctrl 40 PSIG (2.76 Bars)
DP < ctrl_press - diff 40 PSIG (2.76 Bars)
2
Summary of Contents for MILLENNIUM YCAL0043SC
Page 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Page 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Page 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Page 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Page 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Page 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Page 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Page 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Page 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Page 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Page 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Page 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...