This display indicates the status of the evaporator pump
contacts and the evaporator heater.
The evaporator pump dry contacts are energized when
any compressor is running, or the unit is not OFF on
the daily schedule and the unit switch is on, or the unit
has shutdown on a Low Leaving Chilled Liquid fault.
However, even if one of above is true, the pump will not
run if the micropanel has been powered up for less than
30 seconds or if the pump has run in the last 30 sec-
onds to prevent pump motor overheating.
The evaporator heater is controlled by ambient air tem-
perature. When the ambient temperature drops below
40°F the heater is turned on. When the temperature rises
above 45°F the heater is turned off. An under voltage
condition will keep the heater off until full voltage is re-
stored to the system.
There are several types of remote systems that can be
used to control or monitor the unit. The following mes-
sages indicate the type of remote control mode active:
NONE – no remote control active. Remote monitoring
may be via ISN
ISN – YorkTalk via ISN (Remote Mode)
*LOAD LIM – load limiting enabled. Can be either stage
1 or stage 2 of limiting.
*PWM TEMP – EMS-PWM temperature reset
*Refer to the section on Operating Controls
The above four message will appear sequentially, first for
system 1, then for system 2.
The first message indicates the system and number of
compressors that are being commanded on by the mi-
cro board.
The second message indicates the system run time in
days – hours – minutes – seconds. Please note that this
is not accumulated run time but pertains only to the cur-
rent system cycle.
The third message indicates the system, and whether
the liquid line solenoid and hot gas solenoid are being
commanded on by the micro board. Please note that
hot gas in not available for system 2, so there is no mes-
sage pertaining to the hot gas solenoid when system 2
message is displayed.
The fourth message indicates what stage of condenser
fan operation is active. Unless a low ambient kit is added,
only stages 1 and 2 will be used to cycle the condenser
fans. However, stage 3 may be shown in this display
without a low ambient kit added, but it has no effect.
See the section on Condenser Fan Control in the Unit
Operation section.
A C T I V E
R E M O T E
C T R L
N O N E
Unit Controls
Summary of Contents for MILLENNIUM YCAL0043SC
Page 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Page 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Page 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Page 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Page 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Page 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Page 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Page 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Page 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Page 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Page 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Page 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...