YORK INTERNATIONAL
73
FORM 150.62-NM2
Another anti-recycle timer is started each time the sys-
tems number one compressor cycles off. This anti-re-
cycle time is fixed at 120 seconds and starts to count-
down when the systems number one compressor cycles
off.
The anti-recycle message is displayed when the sys-
tem is unable to start due to either of the anti-recycle
timers being active (counting down). The actual time dis-
played will be the longer of the two timers, start-to-start
or stop-to-start.
The Fan Control On Pressure is the programmed pres-
sure value that is used to stage the condenser fans on,
in relation to discharge pressure. Refer to Condenser
Fan Control in the UNIT OPERATION section and Tables
36, 37, and 38, 39.
The Fan Differential Off Pressure is the programmed
differencial pressure value that is used to stage the con-
denser fans off, in relation to discharge pressure. Refer
to Condenser Fan Control in the UNIT OPERATION
section and
Tables 36, 37 and 38, 39.
The TOTAL NUMBER OF COMPRESSORS are the
amount of compressors in the chiller, and determines
the stages of cooling available. Notice in Table 29 her
the chiller is a single or dual refrigerant circuit.
This must be programmed correctly to
assure proper chiller operation.
T O T A L
N U M B E R
O F
C O M P R E S S O R S
=
6
F A N
C O N T R O L
O N
P R E S S U R E = X X X P S I G
FA N
D I F F E R E N T I A L
O F F
P R E S S U R E = X X X P S I G
TABLE 26
– PROGRAM KEY LIMITS AND DEFAULTS
PROGRAM VALUE
MODEL
LOW LIMIT
HIGH LIMIT
DEFAULT
DISCHARGE PRESSURE CUTOUT
—
200 PSIG
399 PSIG
395 PSIG
13.8 BARS
27.5 BARS
27.2 BARS
SUCTION PRESSURE CUTOUT
WATER COOLING
44.0 PSIG
70.0 PSIG
44.0 PSIG
3.03 BARS
4.83 BARS
3.03 BARS
GLYCOL COOLING
20.0 PSIG
70.0 PSIG
44.0 PSIG
1.38 BARS
4.83 BARS
3.03 BAR
LOW AMBIENT TEMP.CUTOUT
STANDARD AMBIENT
25.0°F
60.0°F
25.0°F
-3.9°C
15.6°C
-3.9°C
LOW AMBIENT
0°F
60.0°F
25.0°F
-17.8°C
15.6°C
-3.9°C
LEAVING CHILLED LIQUID
WATER COOLING
—
—
36°F
2.2°C
TEMP. CUTOUT
GLYCOL COOLING
8.0°F
36.0°F
36.0°F
-13.3°C
2.2°C
2.2°C
ANTI-RECYCLE TIMER
—
300 SEC.
600 SEC.
600 SEC.
FAN CONTROL ON-PRESSURE
—
225 PSIG
300 PSIG
230 PSIG
15.5 BARS
20.7 BARS
15.9 BARS
FAN DIFFERENCIAL OFF-PRESSURE
—
50 PSIG
150 PSIG
80 PSIG
3.45 BARS
10.3 BARS
5.52 BARS
TOTAL NUMBER OF COMPRESSORS
SINGLE SYSTEM
2
3
3
TWO SYSTEMS
4
6
6
2
Summary of Contents for MILLENNIUM YCAL0043SC
Page 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Page 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Page 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Page 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Page 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Page 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Page 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Page 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Page 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Page 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Page 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Page 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...