YORK INTERNATIONAL
1
Supersedes: None
Subject: Recommended Operating Guidelines for YCAL Chillers
LITERATURE SUPPLEMENT
Form No.: 150.62-NM2 (LS2)
File with: 150.62-NM2 (699)
201
GENERAL
By observing a few recommended operating guidelines, compressor cycling can be reduced and optimum chilled
liquid temperature control can be achieved when operating YCAL chillers in both water and brine systems.
MINIMUM WATER VOLUME
Minimum water volume in the chilled water system should be 5.0 gallons per ton. Chilled liquid volumes below
this minimum will definitely suffer from chilled liquid temperature control problems and compressor cycling.
Chilled liquid volumes in the range of 7-11 gallons/ton are generally recommended as the industry standard and
will provide the best chilled liquid temperature control with minimum compressor cycling.
MINIMUM LEAVING CHILLED LIQUID CONTROL RANGE PROGRAM SETTINGS
For optimum chilled liquid temperature control, and reduced compressor cycling, leaving chilled liquid setpoint
control range settings should be equal to or greater than the minimum ranges specified in the Table 1 below.
These recommended settings vary according to the number of compressors in the chiller and the chilled liquid
differential actually measured across the evaporator when the chiller is fully loaded. Typically, chilled liquid
system designs utilize an evaporator temperature differential design of 10 ºF, but measurements should be made
to assure that the chiller flows meet design and if not, the minimum control range may need to be varied
accordingly. Use the table below for programming the control range when “leaving” chilled liquid control is
selected.
Recommended Programmed Leaving Chilled Liquid Setpoint
Control Range
Number of
Compressors In
the Chiller
5
º
F Evap Diff
10
º
F Evap Diff
15
º
F Evap Diff
2
± 2.0
º
F
± 2.2
º
F
± 2.5
º
F
3
± 1.8
º
F
± 2.0
º
F
± 2.5
º
F
4
± 1.4
º
F
± 1.8
º
F
± 2.5
º
F
6
± 1.4
º
F
± 1.4
º
F
± 1.8
º
F
TABLE 1 - MINIMUM SETPOINT RANGES
Summary of Contents for MILLENNIUM YCAL0043SC
Page 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Page 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Page 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Page 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Page 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Page 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Page 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Page 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Page 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Page 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Page 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Page 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...