YORK INTERNATIONAL
69
FORM 150.62-NM2
This message indicates that the cooling setpoint is un-
der REMOTE control. When under remote control, the
cooling setpoint will be determined by a remote device
such as an ISN control. The message also indicates that
the control point is based on LEAVING water tempera-
ture out of the evaporator.
This message indicates that the cooling setpoint is un-
der REMOTE control. When under remote control, the
cooling setpoint will be determined by a remote device
such as an ISN control. This message also indicates
that the control point is based on RETURN water tem-
perature into the evaporator.
Immediately after the control mode message is dis-
played, the COOLING SETPOINT entry screen will be
displayed. If the unit is programmed for LEAVING liquid
control the following message will be displayed:
(leaving chilled water control)
The above message shows the current chilled water tem-
perature SETPOINT at 45.0°F (notice the cursor posi-
tioned under the number 5). Pressing either the UP or
DOWN arrow will change the setpoint in .5°F increments.
After using the UP and DOWN arrows to adjust to the
desired setpoint, the ENTER/ADV key must be pressed
to enter this number into memory and advance to the
RANGE SETPOINT.
This will be indicated by the cursor moving under the
current RANGE setpoint. The UP and DOWN arrow keys
are used to set the RANGE, in .5 °F increments,to the
desired RANGE setpoint. After adjusting the setpoint,
the ENTER/ADV key must be pressed to enter the data
into memory.
Notice that the RANGE was programmed for
+/-
X.X° F.
This indicates the SETPOINT to be in the
center
of the
control range. If the control mode has been programmed
for RETURN LIQUID control, the message below would
be displayed in place of the previous message.
(return chilled liquid control)
Notice that the range no longer has a
+/-
X.X °F
, but
only a
+
X.X °F
RANGE setpoint. This indicates that the
setpoint is not centered within the RANGE but could be
described as the bottom of the control rangeA listing of
the limits and the programmable values for the COOLING
SETPOINTS are shown in Table 27.
The SETPOINT and RANGE displays just described
were based on LOCAL control. If the unit was pro-
grammed for REMOTE control (under the OPTIONS
key), the above programmed setpoints would have no
effect.
Both LEAVING and RETURN control are described in
detail under the section on Capacity Control.
R E M 0 T E
L E A V I N G
W A T E R
T E M P
C O N T R O L
S E T P O I N T
=
4 5 . 0 ° F
R A N G E
=
+/-
2 . 0 ° F
R E M O T E
R E T U R N
W A T E R
T E M P
C O N T R O L
S E T P O I N T
=
4 5 . 0
° F
R A N G E
=
+ 2 . 0 ° F
2
Summary of Contents for MILLENNIUM YCAL0043SC
Page 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Page 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Page 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Page 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Page 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Page 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Page 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Page 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Page 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Page 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Page 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Page 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...