NOTES:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the
rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the Factory Mounted Control
Transformer is provided, add the following to the system MCA values in the electrical tables for the system
supplying power to the optional transformer. -50, add 1.75 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included in
the circuit. Local codes must be complied with.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not
recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at
ambient temperatures in excess of 95°F is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit, per N.E.C. Article 440-22.
5. Circuit breakers must be U.L. listed and CSA certified and maximum size is based on 225% of the rated load
amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Exception:
YCA0043 and YCAL0057 must have the optional factory overloads installed to use a standard circuit breaker.
Otherwise, an HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is based on
225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included
in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the unit
wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of
the wire range specified. Actual wire size and number of wires per phase must be determined based on the
National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C.
Table 250-95. A control circuit grounding lug is also supplied.
8. The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating
the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not
intended to be a Load Break Device.
9. Field Wiring by others which complies to the National Electrical Code and Local Codes.
ELECTRICAL NOTES
1
Summary of Contents for MILLENNIUM YCAL0043SC
Page 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Page 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Page 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Page 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Page 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Page 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Page 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Page 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Page 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Page 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Page 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Page 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...