– WIRING DIAGRAM – ACROSS-THE-LINE START
WIRING DIAGRAM
ACROSS-THE-LINE START
7
NOTES:
1. Field wiring to be in accordance with the current edition
of the National Electrical Code as well as all other appli-
cable codes and specifications.
2 . Contacts must be suitable for switching 24VDC. (Gold
contacts recommended). Wiring shall NOT run in the
same conduit with any line voltage (Class 1) wiring.
3. To cycle unit ON and OFF automatically with contacts
shown, install a cycling device in series with the flow
switch. See Note 2 for contact rating and wiring specifi-
cations.
4. To stop unit (Emergency Stop) with contacts other than
those shown, install the stop contact between 5 and 1. If a
stop device is not installed, a jumper must be connected
between terminals 5 and 1. Device must have a minimum
contact rating of 6A at 115 volts A.C.
5. Contacts are rated at 115V, 100VA, resistive load only,
and must be suppressed at load by user.
LD06012
LD06013
UNIT
CONTROL
MIN.
MAX DUAL NON FUSED
VOLTAGE
POWER
CIRCUIT ELEMENT
DISC.
SUPPLY
AMP
FUSE SIZE FUSE SIZE
ALL MODELS
115-1-50/60
20A
20A 250V
30A 240V
W/O TRANS
CONTROL POWER SUPPLY
Summary of Contents for MILLENIUM YCAS Series
Page 47: ...47 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 63: ...63 YORK INTERNATIONAL FORM 201 18 NM6 7 WIRING DIAGRAM WYE DELTA START LD06015...
Page 68: ...68 YORK INTERNATIONAL Technical Data LEGEND 0283 0343 LD06179...
Page 69: ...69 YORK INTERNATIONAL FORM 201 18 NM6 7 LD05957...
Page 70: ...70 YORK INTERNATIONAL Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06019...
Page 71: ...71 YORK INTERNATIONAL FORM 201 18 NM6 7 COMPRESSOR TERMINAL BOX LD06020...