SWITCH 2: Ambient Temp. Low Limit
Open:
Standard Ambient Mode auto-programs the Low Am-
bient Cutout setting at -4°C (25°F) and is not adjust-
able.
Closed:
Low Ambient Mode allows the Low Ambient Cut-Out
to be programmed from -18 to 10°C (0 to 50 °F). Val-
ues above -4°C (25°F) can be used to automatically
shut down the chiller when direct cooling methods be-
come operational.
SWITCH 3: Refrigerant
Open:
The R-407C Mode MUST be selected for models us-
ing refrigerant R-407C. Incorrect selection of this
switch may cause serious damage to the chiller.
Closed:
The R-22 Mode MUST be selected for models using
refrigerant type R-22. Incorrect selection of this switch
may cause serious damage to the chiller.
S 1 - 2
A M B I E N T
C O N T R O L
S T A N D A R D
S 1 - 2
A M B I E N T
C O N T R O L
L O W
A M B I E N T
S 1 - 3
R E F R I G E R A N T
R - 4 0 7 C
S 1 - 3
R E F R I G E R A N T
R - 2 2
Dip Switch Physical Location and Setting
FIG. 40
– ENLARGED PHOTOGRAPH OF DIP
SWITCHES ON MICROPROCESSOR
BOARD
LD03511A
LD03511B
“OPEN” Position:
Left side of switch
pushed in
“CLOSED” Position:
Right side of switch
pushed in
Micro Panel Contents
Summary of Contents for MILLENIUM YCAS Series
Page 47: ...47 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 63: ...63 YORK INTERNATIONAL FORM 201 18 NM6 7 WIRING DIAGRAM WYE DELTA START LD06015...
Page 68: ...68 YORK INTERNATIONAL Technical Data LEGEND 0283 0343 LD06179...
Page 69: ...69 YORK INTERNATIONAL FORM 201 18 NM6 7 LD05957...
Page 70: ...70 YORK INTERNATIONAL Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06019...
Page 71: ...71 YORK INTERNATIONAL FORM 201 18 NM6 7 COMPRESSOR TERMINAL BOX LD06020...