109
YORK INTERNATIONAL
FORM 201.18-NM6
2. STATUS KEY: GENERAL STATUS MESSAGES & FAULT WARNINGS
2.1
GENERAL
Pressing the Status key displays the current chiller or
individual system operational status. The messages dis-
played include running status, cooling demand, fault
status, external cycling device status, load limiting, and
anti-recycle timer status. The display will show one mes-
sage relating to the “highest priority” information as
determined by the microprocessor.
For individual system status or fault messages, the dis-
play shows information for up to two refrigerant sys-
tems.
The main categories of messages available using the
Status key are:
2.2
General Status Messages
2.3
Unit Warnings
2.4
Anticipation Control Status Messages
2.5
Chiller Fault Status Messages
2.6
System Fault Status Messages
These messages are described in detail below, with ex-
amples of each display. In each example “#” is used as
applicable to represent the system number where mes-
sages apply to individual systems.
2.2
GENERAL STATUS MESSAGES
Unit Switch OFF:
This message indicates that the Chiller ON / OFF Switch
on the Control Panel is in the OFF position which will
not allow the chiller to run.
Schedule Shutdown:
This message indicates that the that the chiller has been
shut down by the daily schedule programmed into the
Clock - Set Schedule / Holiday system (Section 7.3).
Compressors Running:
This message indicates that the respective compressor
is running due to demand.
Remote Controlled Shutdown:
This message indicates that either an ISN or RCC (Re-
mote Control Center) has turned the unit OFF through
the RS-485 port.
U N I T
S W I T C H
O F F
S H U T D O W N
D A I L Y
S C H E D U L E
S H U T D O W N
S Y S
#
C O M P
R U N N I N G
S Y S
#
C O M P
R U N N I N G
R E M O T E
C O N T R O L L E D
S H U T D O W N
29023A
8
Summary of Contents for MILLENIUM YCAS Series
Page 47: ...47 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 63: ...63 YORK INTERNATIONAL FORM 201 18 NM6 7 WIRING DIAGRAM WYE DELTA START LD06015...
Page 68: ...68 YORK INTERNATIONAL Technical Data LEGEND 0283 0343 LD06179...
Page 69: ...69 YORK INTERNATIONAL FORM 201 18 NM6 7 LD05957...
Page 70: ...70 YORK INTERNATIONAL Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06019...
Page 71: ...71 YORK INTERNATIONAL FORM 201 18 NM6 7 COMPRESSOR TERMINAL BOX LD06020...