117
YORK INTERNATIONAL
FORM 201.18-NM6
is unlikely to occur unless a problem exists in the mea-
suring sensors or during extreme conditions.
The Display keys and the data available from each is as
follows:
3.2
CHILLED LIQUID TEMPS KEY
When the Chilled Liquid Temperatures key is pressed
a display of chilled liquid temperatures leaving the
chiller (LCHLT) and returning to the chiller (RCHLT)
is provided as follows:
If the key is pressed again, the following message will
appear if an optional mixed chilled leaving temp sen-
sor is installed for multi unit sequencing. If a sensor is
not installed, pressing the key will have no effect.
3. DISPLAY KEYS & OPTION SWITCHES
3.1
GENERAL
The Display keys provide direct access to retrieve com-
monly required data about the operation of the chiller.
This is particularly useful during commissioning, moni-
toring the operation of the chiller, diagnosing potential
future problems and service troubleshooting.
When a Display key is pressed, the corresponding mes-
sage will be displayed and will remain on the display
until another key is pressed.
Displayed data is in “real-time” and is updated approxi-
mately every 2 seconds. If updating of one of the mes-
sages is required faster than every 2 seconds, the ap-
propriate key for the desired display can be pushed and
held to provide updating every 0.4 seconds.
Display Messages may show characters indicating
“greater than” (>) or “less than” (<). These characters
indicate the actual values are greater than or less than
the values which are being displayed, but are outside
the ability of the micro to give an actual reading. This
L C H L T
=
6 . 8
°
C
R C H L T
=
1 2 . 2
°
C
M C H L T
=
6 . 6
°
C
29023A
8
Summary of Contents for MILLENIUM YCAS Series
Page 47: ...47 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 63: ...63 YORK INTERNATIONAL FORM 201 18 NM6 7 WIRING DIAGRAM WYE DELTA START LD06015...
Page 68: ...68 YORK INTERNATIONAL Technical Data LEGEND 0283 0343 LD06179...
Page 69: ...69 YORK INTERNATIONAL FORM 201 18 NM6 7 LD05957...
Page 70: ...70 YORK INTERNATIONAL Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06019...
Page 71: ...71 YORK INTERNATIONAL FORM 201 18 NM6 7 COMPRESSOR TERMINAL BOX LD06020...