119
YORK INTERNATIONAL
FORM 201.18-NM6
3.7
OPTIONS KEY &
DIP SWITCH SETTINGS
The Options key provides a display of options which
are programmed by the positions of the S1 Dip Switches
on the Microprocessor Board. Proper programming of
the switches is important during the commissioning of
the chiller. The Options key can be used to verify the
Dip Switch positions without looking at or handling
the Microprocessor Board.
Each press of the key will scroll to the next option/dip
switch setting.
Three Option Switch Messages (S1-1 to S1-3) will then
be displayed in sequence. At the end of the sequence,
the display will automatically revert to the first Option
Switch message.
The following is a detailed guide to programming the
Dip Switches together with the associated display mes-
sage provided for each selection when the Options key
is pressed:
SWITCH 1: Water / Brine Cooling
Open:
Water Cooling Mode is for water cooling applications
and allows the chilled liquid leaving temperature setpoint
to be programmed from 4 to 21°C (40 to 70 °F). Select-
ing this mode also auto-programs the Low Chilled Liquid
Cut-Out at 2°C (36°F) and the Suction Pressure Cut-
Out at 3 bar (44 PSIG).
Closed:
Brine Cooling Mode is for brine/glycol applications with
setpoints below 4°C (40°F) and allows the chilled liquid
leaving temperature setpoint to be programmed from 10
to -12 - 21°C (70°F). In this mode, the Low Chilled Liq-
uid Cut-Out can be programmed from -13 to 2°C (8 to
36° F) and the Suction Pressure Cut-Out programmed
from 1 to 5 bar (20 to 70 PSIG) for R-22 models and 0.3
to 5 bar (5 to 70 PSIG) for R-407c models.
3.5
MOTOR CURRENT KEY
Pressing the Motor Current key displays compressor
current for each system:
This display shows the average motor current in amps
and average compressor motor current as a percentage
of FLA. All values are approximate. Keep in mind that
current in “amps” is an “approximate” value.
On the second press of the of the Motor Current Key,
the current limit values as set by the ISN (Remote BAS
System) and EMS-PWM current limiting input are dis-
played, if they are active. See Sections 1.10, and 2.4
for more details.
3.6
OPERATING HRS / START COUNTER KEY
When the Operating Hours / Starts Counter key is
pressed, the accumulated running hours and starts for
System 1 and 2 compressors are displayed. Where ap-
plicable, pressing the key again displays the values for
Systems 3 and 4 on larger models:
Display Limits : Maximum run hours 99,999
Maximum starts 99,999
Values roll over to zero, if the maximum limit is exceeded.
These counters are zeroed at the fac-
tory, but may indicate run time and
number of starts logged during factory
testing prior to shipment.
H R S
1 =
1 1 4 3 . 2
=
1 3 8 2
S T R
1 =
2 8 5 . 2
=
3 2 2
H R S
3 =
1 2 5 5 . 4
=
1 0 9 5
S T R
3 =
3 6 5 . 4
=
4 5 5
S 1 - 1
C H I L L E D
L I Q U I D
W A T E R
S 1 - 1
C H I L L E D
L I Q U I D
G L Y C O L
C O M P
1 = 6 3
A M P
8 5 % F L A
C O M P
2 = 3 0
A M P
4 1 % F L A
I S N
C R N T
L I M I T :
N O N E
E M S
C R N T
L I M I T :
N O N E
8
Summary of Contents for MILLENIUM YCAS Series
Page 47: ...47 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 63: ...63 YORK INTERNATIONAL FORM 201 18 NM6 7 WIRING DIAGRAM WYE DELTA START LD06015...
Page 68: ...68 YORK INTERNATIONAL Technical Data LEGEND 0283 0343 LD06179...
Page 69: ...69 YORK INTERNATIONAL FORM 201 18 NM6 7 LD05957...
Page 70: ...70 YORK INTERNATIONAL Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06019...
Page 71: ...71 YORK INTERNATIONAL FORM 201 18 NM6 7 COMPRESSOR TERMINAL BOX LD06020...