118
YORK INTERNATIONAL
Slide valve position is APPROXI-
MATE and should be used for refer-
ence only. Under actual conditions the
compressor may be fully loaded be-
tween step 60 - 75 and fully unloaded
between step 0 - 40.
Superheats are the difference between the respective satu-
rated temperature (converted from pressure) and the ac-
tual. Display Limits for the System Pressures and Tem-
peratures displays are as follows:
Minimum and maximum values may
change as software (EPROM) revi-
sions are made.
*Below 13°C (9.0°F), the Suction
Temp. display will disappear. This will
in turn cause the Superheat display to
disappear.
3.4
AMBIENT TEMP KEY
When the Ambient Temperature key is pressed, ambi-
ent air temperature, as measured surrounding the chiller,
is displayed.
Display Limits: Minimum
-20.3°C
(-4.6°F)
Maximum
58.8°C (137.9°F)
3.3
SYSTEM # DATA KEYS
Pressing one of the System # Data keys a number of
times scrolls through displays of differential oil pres-
sure (OIL), suction pressure (SP) and discharge pres-
sure (DP), oil temperature, suction temperature (ST),
discharge temperature (DT), saturated suction tempera-
ture, suction superheat, saturated discharge tempera-
ture, discharge superheat and compressor slide valve
position.
Examples of these displays are as follows where # is
the appropriate system number:
The Cooler Inlet Temp. display will
only appear if the chiller is selected for
R-407c.
Temperatures and pressures are either measured directly
by transducers and temperature sensors, or computed
from these measurements as follows:
Saturated discharge and suction temperatures are com-
puted by converting measured pressure to temperature.
Slide Valve Position is computed based on the number
of loading steps that the micro has sent to the slide valve
solenoid in the form of a current signal. To the micro-
processor, STEP 0 = fully unloaded and STEP 75 =
fully loaded.
A M B I E N T
A I R
T E M P
=
2 2 . 2
° C
S #
S A T
D S C H =
5 4 . 4 ° C
D S C H
S H E A T
=
3 0 . 7 ° C
S Y S
#
S
V
S T E P
=
3
S Y S
#
C O O L E R
I N L E T
R E F R I G
T E M P =
- 2 . 1 ° C
S Y S
#
O I L =
1 2 . 1
B A R G
S P =
6 4
D P = 1 3 . 5
B A R G
S Y S
#
O I L
=
6 9 . 7 ° C
S T =
3 1 . 0
D T =
5 0 . 7 ° C
S #
S A T
S U C T
=
6 . 9 ° C
S U C T
S H E A T
=
8 . 3 ° C
MIN. LIMIT
MAX. LIMIT
Oil Pressure
14 Bar (208 PSID)
0 Bar
(0 PSID)
Suction Pressure
0 Bar
(0 PSIG)
14 Bar (199 PSIG)
Discharge Pressure
0 Bar
(0 PSIG)
28 Bar (399 PSIG)
Suction Temp.
*-13°C
(9.0 °F)
29°C
(84.2 °F)
Discharge Temp.
5°C
(40.3 °F)
150°C
(302.6 °F)
Oil Temp.
5°C
(40.3 °F)
116°C
(240.0 °F)
Sat. Discharge Temp.
-41°C
(-41.0 °F)
60°C
(140.5 °F)
Sat. Suction Temp.
-41°C
(-41.0 °F)
39°C
(101.3 °F)
Slide Valve Position
0 %
(0%)
100%
(100%)
Suction Superheat
*-63.1°C
(-81.5 °F)
16°C
(60.9 °F)
Discharge Superheat
-5.3°C
(22.5 °F)
102.2°C
(216.0 °F)
Micro Panel Contents
Summary of Contents for MILLENIUM YCAS Series
Page 47: ...47 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM6 7 This page intentionally left blank...
Page 63: ...63 YORK INTERNATIONAL FORM 201 18 NM6 7 WIRING DIAGRAM WYE DELTA START LD06015...
Page 68: ...68 YORK INTERNATIONAL Technical Data LEGEND 0283 0343 LD06179...
Page 69: ...69 YORK INTERNATIONAL FORM 201 18 NM6 7 LD05957...
Page 70: ...70 YORK INTERNATIONAL Technical Data CONNECTION DIAGRAM SYSTEM WIRING LD06019...
Page 71: ...71 YORK INTERNATIONAL FORM 201 18 NM6 7 COMPRESSOR TERMINAL BOX LD06020...