30
than 24V, current less than 0.5A
3. When the unit occurs the problem, the relay would be closed, then ALARM works
C. For new fresh motor terminal port CN14&CN14
1. Connect the fan motor to the port, no need care L/N of the motor;
2. The output voltage is the power supply;
3. The fresh motor cannot excess 200W or 1A, follow the smaller one;
4. The new fresh motor will be worked when the indoor fan motor work ;when the indoor fan motor stops,
the new fresh motor would be stopped;
5. When the unit enter force cooling mode or capacity testing mode, the fresh motor isn’t work.