28
than 24V, current less than 0.5A
3. When the unit occurs the problem, the relay would be closed, then ALARM works
C. For new fresh motor terminal port CN8
1. Connect the fan motor to the port, no need care L/N of the motor;
2. The output voltage is the power supply;
3. The fresh motor cannot excess 200W or 1A, follow the smaller one ;
4. The new fresh motor will be worked when the indoor fan motor work ;when the indoor fan motor
stops , the new fresh motor would be stopped ;
5. When the unit enter force cooling mode or capacity testing mode, the fresh motor isn’t work .
YFKE18BXTMCM-RX
,
YFJE18BXTMCM-RX, YFKE24BXTMCM-RX
,
YFJE24BXTMCM-RX,