111
16.4.15. J3 Malfunction
Malfunction decision conditions
When the voltage signal that IPM send to compressor drive chip is abnormal, the
display LED will show “J3” and AC will turn off.
Supposed causes
●
Wiring mistake
●
Faulty IPM board
●
Faulty outdoor fan ass’y
●
Compressor malfunction
●
Faulty outdoor PCB
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0
or close to 0, the IPM is defective. Otherwise, please follow the procedure below: