16.4.12. J0 Malfunction
Malfunction conditions
When evaporator coil temperature is more than 60°C, the unit stops. It starts again
only when the evaporator coil temperature is less than 54°C
Possible causes
Faulty evaporator coil temperature sensor
Dirty heat exchanger
Faulty fan
Faulty PCB