Sequence of Operation
FORM 100.50-NOM1 (604)
◦
If the (By-pass Percentage Setpoint – 2.5
0
F) <
Actual By-pass Setpoint < (By-pass Percentage
Se 2.5
0
F) the bypass damper will not
move.
• A change in the By-pass Damper position will only
be allowed to occur 2 minutes after a compressor is
started or stopped.
• Immediately after a compressor is started and
stopped, the By-pass Damper will be
Þ
xed by the
Primary Unit Controller
• The Primary Unit Controller will not open or close
the By-pass Damper until the SAT temperature fall
below the RAT.
• If the SAT temperature is above the RAT, the By-pass
Damper shall remain
Þ
xed.
By-pass
Percentage
Setpoint
By-pass
Percentage
Se
2.5
0
%
By-pass
Percentage
Setpoint-
2.5
0
%
DRIVE
OPEN
IDLE
DRIVE
CLOSED
BYPASS
DAMPER
FIG. 46 –
BYPASS DAMPER SETPOINTS