23
YORK INTERNATIONAL
2
FORM 100.50-NOM1 (604)
ELECTRIC HEAT
TABLE 4 – AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS
TABLE 3 – ELECTRICAL DATA (CONTINUED)
* Cooling Only Units
KW
NOMINAL VOLTAGE
208/3/60
AMPS
230/3/60
AMPS
460/3/60
AMPS
575/3/60
AMPS
40
96
96
48
40
80
193
193
96
80
108
260
260
130
109
150
—
—
181
151
200
—
—
241
201
250
—
—
301
251
Limitations
Model Size
50
55
60
65
70
75
80
85
90
95
Design Airfl ow Limits
CFM* (min to max)
10000 -
22500
12000 -
24000
14000 -
27000
14000 -
27000
14000 -
32000
14000 -
32000
14000 -
32000
14000 -
32000
18000 -
36000
18000 -
36000
Entering Wet Bulb
Temp F° (min/max)
57/75
57/75
57/75
57/75
57/75
57/75
57/75
57/75
57/75
57/75
Entering Dry Bulb
Temp F° (min/max)
68/90
68/90
68/90
68/90
68/90
68/90
68/90
68/90
68/90
68/90
Ambient Temp F°
without Low Amb option
45/120
45/120
45/120
45/120
45/120
45/120
45/120
45/120
45/120
45/120
Ambient Temp F°
with Low Amb option
0/120
0/120
0/120
0/120
0/120
0/120
0/120
0/120
0/120
0/120