5120410-XIM-B-0216
52
Johnson Controls Unitary Products
Any time the UCB senses voltage at the GV without a call for
heat for a continuous five-minute period, the UCB will lock-on
the indoor blower and a flash code is initiated (Table 37). When
voltage is no longer sensed at the GV, the UCB will de-energize
the indoor blower following the elapse of the fan off delay for
heating.
If voltage has been sensed at the GV for at least 15 seconds
during the fan on delay for heating and GV voltage or “W1” is
lost, the indoor blower is forced on for the length of the fan off
delay for heating.
During a call for heat, if the UCB does not sense voltage at the
GV for a continuous five-minute period the UCB will initiate a
flash code (Table 37). The indoor blower motor will not be
locked-on while there is no GV voltage.
Safety Controls
The UCB monitors the temperature limit switch of gas heat
units.
The control circuit includes the following safety controls:
Limit Switch (LS)
This control is located inside the gas heat compartment and is
set to open at the temperature indicated in the Gas Heat Limit
Control Settings Table 33. It resets automatically. The limit
switch operates when a high temperature condition, caused by
inadequate supply air flow occurs, thus shutting down the
heater and energizing the blower.
Auxiliary Limit Switch (ALS)
This control is located inside the supply air compartment and is
set to open at the temperature indicated in the Gas Heat Limit
Control Settings Table 33. It resets manually. The limit switch
operates when a high temperature condition, caused by
inadequate supply air flow occurs, thus shutting down the
heater and energizing the blower.
The auxiliary limit switch is wired in series with the limit switch.
As such, the UCB cannot distinguish the auxiliary limit and the
gas heat limit switch operation except the auxiliary is manual
reset. Consequently, the control will respond in the same
manner as outlined above under “Limit Switch”.
The ICB monitors the Pressure and Rollout switches of gas
heat units.
The control circuit includes the following safety controls:
Pressure Switch (PS)
Once the draft motor has reached full speed and closes the
pressure switch during a normal ignition sequence, if the
pressure switch opens for 2 seconds, the GV will be de-
energized, the ignition cycle is aborted, and the ICB flashes the
appropriate code. See Table 37 Ignition Control Flash Codes.
The draft motor is energized until the pressure switch closes or
“W1” is lost.
Rollout Switch (ROS)
The rollout switch is wired in series with the pressure switch. As
such, the ICB cannot distinguish the rollout switch operation
from that of the pressure switch.
Consequently, the control will only respond in the same manner
as outlined above under “Pressure Switch”. An open rollout will
inhibit the gas valve from actuating.
Internal Microprocessor Failure
If the ICB detects an internal failure, it will cease all outputs,
ignore inputs, and display the proper flash code for control
replacement. The ICB remains in this condition until replaced.
Flash Codes
The ICB will initiate a flash code associated with errors within
the system. Refer to Ignition Control Flash Codes Table 37.
Resets
Remove the call for heating by lowering the thermostat setting
lower than the conditioned space temperature. This resets any
flash codes.
Gas Heat Anticipator Setpoints
It is important that the anticipator setpoint be correct. Too high
of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter “ON cycles
and may result in the lowering of the temperature within the
conditioned space. Refer to Table 34 for the required gas heat
anticipator setting.
Table 33: Gas Heat Limit Settings
1
1.Rollout = 300°F (148.9°C), Auxiliary Limit = 200°F (93.3°C)
Unit
Main Limit Setting
Size
Opt. Natural
Gas
LPG
DC090
10
165°F (73.9°C)
175°F (79.4°C)
15
165°F (73.9°C)
185°F (85°C)
DC120
15
195°F (90.5°C)
195°F (90.5°C)
20
150°F (65.6°C)
150°F (65.6°C)
DC150
15
195°F (90.5°C)
195°F (90.5°C)
20
160°F (71.1°C)
160°F (71.1°C)
Table 34: Gas Heat Anticipator Setpoints
SETTING, AMPS
W1
W2
0.65
0.1