![background image](http://html1.mh-extra.com/html/york/dc-series/dc-series_installation-manual_912439021.webp)
5120410-XIM-B-0216
Johnson Controls Unitary Products
21
Table 13: Electrical Data
Voltage
1
1. Unit voltage limitations: minimum utilization 342 volts, maximum utilization 457 volts.
Compressors
OD Fan
Motors
Supply
Blower Motor
FLA
Pwr Exh
Motor
Electric Heater
Model No.
Actual
kW
Heater
Amps
Min. Circuit
Ampacity
(Amps)
MCA w/
Power
Exhaust
(Amps)
Max Fuse
2
2. Maximum HACR breaker of the same amp size is acceptable.
Size (Amps)
Max Fuse Size
w/Power
Exhaust (Amps)
RLA
ea.
LRA
ea.
FLA
ea.
2 HP
(1.5 kW)
FLA
2 HP
(1.5 kW)
2 HP
(1.5 kW)
2 HP
(1.5 kW)
2 HP
(1.5 kW)
380
8.0
53
1.1
5.2
2.2
None
-
-
25.4
27.6
30
35
2TP04541850
3
3. Field Installed Kit Only.
11.3
17.2
28.0
30.8
30
35
415
8.0
53
1.1
5.2
2.2
None
-
-
25.4
27.6
30
35
2TP04541850
3
13.5
18.8
30.0
32.8
30
35
Voltage
1
Compressors
OD
Fan
Motors
Supply Blower
Motor FLA
Pwr Exh
Motor
Electric
Heater
Model No.
Actual
kW
Heater
Amps
Min. Circuit
Ampacity
(Amps)
MCA
w/Power
Exhaust
(Amps)
Max Fuse
2
Size (Amps)
Max Fuse Size
w/Power
Exhaust
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
2 HP
(1.5 kW)
4 HP
(3 kW)
FLA
2 HP
(1.5 kW)
4 HP
(3 kW)
2 HP
(1.5 kW)
4 HP
(3 kW)
2 HP
(1.5 kW)
4 HP
(3 kW)
2 HP
(1.5
kW)
4 HP
(3
kW)
380
9.6
80
1.1
5.2
7.5
2.2
None
-
-
29.0
31.3
31.2
33.5
35
40
40
40
2TP04521850
11.3
17.2
29.0
31.3
31.2
33.5
35
40
40
40
2TP04522450
15.0
22.8
35.0
37.9
37.7
40.6
35
40
40
45
2TP04523650
21.3
32.4
47.0
49.8
49.7
52.6
50
50
50
60
2TP04525450
33.8
51.4
70.7
73.6
73.4
76.3
80
80
80
80
415
9.6
80
1.1
5.2
7.5
2.2
None
-
-
29.0
31.3
31.2
33.5
35
40
40
40
2TP04521850
13.5
18.8
30.0
32.9
32.7
35.6
35
40
40
40
2TP04522450
17.9
24.9
37.6
40.5
40.4
43.3
40
45
45
45
2TP04523650
25.4
35.3
50.7
53.5
53.4
56.3
60
60
60
60
2TP04525450
40.4
56.2
76.8
79.6
79.5
82.4
80
80
80
90
Electrical data 12-1/2 ton
Voltage
1
Compressors
OD
Fan
Motors
Supply Air
Blower
Motor FLA
Pwr Exh
Motor
Electric
Heater
Model No.
Actual
kW
Heater
Amps
Min. Cir-
cuit
Ampacity
(Amps)
MCA
w/Power
Exhaust
(Amps)
Max
Fuse
2
Size
(Amps)
Max Fuse
Size
w/Power
Exhaust
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
4 HP (3 kW)
FLA
4 HP
(3 kW)
4 HP
(3 kW)
4 HP
(3 kW)
4 HP
(3 kW)
380
12.0
91
1.1
7.5
2.2
None
-
-
36.7
38.9
45
50
2TP04521850
11.3
17.2
36.7
38.9
45
50
2TP04522450
15.0
22.8
37.9
40.6
45
50
2TP04523650
21.3
32.4
49.8
52.6
50
60
2TP04525450
33.8
51.4
73.6
76.3
80
80
415
12.0
101
1.1
7.5
2.2
None
-
-
36.7
38.9
45
50
2TP04521850
13.5
18.8
36.7
38.9
45
50
2TP04522450
17.9
24.9
40.5
43.3
45
50
2TP04523650
25.4
35.3
53.5
56.3
60
60
2TP04525450
40.4
56.2
79.6
82.4
80
90
1. Unit voltage limitations: minimum utilization 342 volts, maximum utilization 457 volts.
2. Maximum HACR breaker of the same amp size is acceptable.
Electrical data 7-1/2 ton
Electrical data 10 ton
1. Unit voltage limitations: minimum utilization 342 volts, maximum utilization 457 volts.
2. Maximum HACR breaker of the same amp size is acceptable.