47
Table 29: Additional Static Resistance DC120/150 Cabinet (Metric)
M
3
S
Cooling Only
1
1. Add these resistance values to the available static resistance in the respective Blower Performance Tables.
Economizer
2
3
2. Deduct these resistance values from the available external static pressure shown in the respective Blower Perfor-
mance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of
the return air duct system is less than 62.1 Pa, the unit will deliver less M3S during full economizer operation.
Electric Heat kW
2
18
24
36
54
0.89
14.9
5.0
14.9
17.4
19.9
24.8
0.99
17.4
5.0
17.4
19.9
22.4
27.3
1.08
19.9
5.0
19.9
22.4
24.8
32.3
1.18
22.4
5.0
22.4
24.8
27.3
34.8
1.27
27.3
7.5
24.8
29.8
32.3
39.7
1.36
29.8
7.5
27.3
32.3
34.8
44.7
1.46
34.8
7.5
32.3
37.3
39.7
49.7
1.55
39.7
7.5
34.8
42.2
44.7
54.6
1.65
44.7
9.9
39.7
47.2
49.7
59.6
1.74
49.7
9.9
44.7
52.2
49.7
64.6
1.83
57.1
9.9
49.7
57.1
59.6
69.5
1.93
62.1
9.9
54.6
62.1
64.6
77.0
1.02
69.5
12.4
59.6
69.5
72.0
84.4
2.12
74.5
12.4
64.6
74.5
77.0
91.9
2.21
82.0
12.4
72.0
82.0
84.4
99.3
2.30
89.4
12.4
77.0
86.9
91.9
106.8
2.40
96.9
14.9
84.4
94.4
99.3
114.2
2.49
104.3
14.9
91.9
101.8
106.8
121.7
2.59
111.8
14.9
99.3
109.3
114.2
131.6
2.68
119.2
14.9
106.8
116.7
121.7
139.1
2.77
129.1
17.4
114.2
124.2
131.6
146.5
2.87
139.1
17.4
121.7
131.6
139.1
154.0
2.96
149.0
17.4
131.6
139.1
146.5
161.4
Table 30: Additional Static Resistance DC090 Cabinet (Metric)
M
3
S
Cooling Only
1
Economizer
2
3
0.9
-0.99
17.40
0.99
2.50
22.40
1.09
2.50
27.40
1.18
4.98
32.40
1.27
7.50
39.90
1.37
10.00
44.83
1.46
12.50
49.81
1.56
14.90
54.80
1.65
17.40
59.80
1.75
19.90
67.20
1.84
22.40
72.20
1.93
22.40
77.20
2.03
24.90
82.20
1. Add these resistance values to the available static resistance in the respective Blower
Performance Tables.
2. Deduct these resistance values from the available external static pressure shown in
the respective Blower Performance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for
100% return air. If the resistance of the return air duct system is less than 62.1 Pa, the
unit will deliver less M3S during full economizer operation.