background image

DUCT COVERS - Units are shipped with all air duct
openings covered.
For side duct applications;
1. Remove and discard the supply and return air duct
    covers.
2. Connect ductwork to duct flanges on the rear of the
    unit.
For bottom duct applications;
1. Remove the side supply and return air duct covers to
    gain access to the bottom supply and return air duct 
    covers.
2. Remove and discard the bottom duct covers.
3. Replace the side duct covers.

FIG. 10 - DIMENSIONS & CLEARANCES- 7-1/2 – 12-1/2 TON

All dimensions are in inches. They are subject
to change without notice. Certified dimensions
will be provided upon request.

HOLE

OPENING

SIZE

(DIA.)

USED FOR

A

3/4" KO

Control 
Wiring

Side

7/8" KO

Bottom*

B

2"  KO

Power Wiring
(Side or Bottom)*

C

2" KO

Gas Piping (Front)

D

1-11/16" KO

Gas Piping (Bottom)*

 *

Openings in the bottom of the unit can be located by the slice in the

   insulation.

UTILITIES ENTRY DATA

RETURN AIR

OUTDOOR AIR

(Economizer)

SUPPLY AIR

CONDENSER AIR

CLEARANCES

Front

24"

Back

12" (Less Economizer)
36" (With Economizer)

Left Side (Filter Access)

24" (Less Economizer)
54" (With Economizer)

Right Side (Cond. Coil)

24"

Below Unit

1

2

0"

Above Unit

2

72" with 36" maximum
   Horizontal Overhang
     (For Condenser Air Discharge)

Locate unit so that the vent air outlet hood is at least:

 Three (3) feet above any forced air inlet located within 10 horizontal feet (excluding

   those integral to the unit).

 Four (4) feet below, 4 horizontal feet from, or 1 foot above any door or gravity air inlet

   into the building.

 Four (4) feet from electric meters, gas meters, regulators and relief equipment.

2

Units (applicable in U.S.A. only) may be installed on combustible floors made from

  wood or class A, B or C roof covering material.

3

 Units must be installed outdoors. Overhanging structures or shrubs should not

   obstruct the condenser air discharge outlet.
NOTE: A 1" clearance must be provided between any combustible material and the
   supply air ductwork for a distance of 3 feet from the unit.
   The products of combustion must not be allowed to accumulate within a confined
   space and recirculate.

530.18-N10Y

Unitary Products Group

9

Summary of Contents for D3CG090

Page 1: ...ting of replacement parts on this equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York Pa 17405 APPROVALS De...

Page 2: ...ication Data 3 2 Gas Heat Application Data 5 3 Pipe Sizing 5 4 Physical Data 8 5 Supply Air Blower Perf 7 1 2 10 Ton 10 6 Supply Air Blower Perf 12 1 2 Ton 11 7 Accessory Static Resistances 11 8 Blowe...

Page 3: ...holes provided in the base rails Spreaders whose length exceeds the largest dimension across the unit MUST be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIB...

Page 4: ...re replaced on the unit to maintain an air tight seal THERMOSTAT The room thermostat should be located on an inside wall approximately 56 above the floor where it will not be subject to drafts sun exp...

Page 5: ...ocal codes or gas company requirements Refer to Table 3 The heating value of the gas may differ with locality The value should be checked with the local gas utility NOTE There may be a local gas utili...

Page 6: ...oad Maintaining proper gas pressure depends on three main factors 1 The vaporization rate which depends on a the temperature of the liquid and b the wetted surface area of the container or containers...

Page 7: ...ing 6 gasketed screws in each side plate 4 Secure the flange on the hood cover to the duct panel with 3 screws Use holes in the cover flange as a template and drill 3 holes 9 64 dia 26 drill into the...

Page 8: ...t 7 8 9 1 10 9 13 4 OUTDOOR FAN Two Per Unit PROPELLER DIA in 24 ea 24 ea 24 ea 24 ea FAN MOTOR HP 1 2 ea 1 2 ea 1 2 ea 3 4 ea NOM CFM TOTAL 2900 ea 3200 ea 3600 ea 4400 ea CONDENSER COIL ROWS DEEP 2...

Page 9: ...R CLEARANCES Front 24 Back 12 Less Economizer 36 With Economizer Left Side Filter Access 24 Less Economizer 54 With Economizer Right Side Cond Coil 24 Below Unit1 20 Above Unit2 72 with 36 maximum Hor...

Page 10: ...9 1 54 1 44 0 04 1 75 1 63 1070 0 86 1 46 1 36 0 54 1 68 1 57 0 20 1 89 1 76 0 04 2 11 1 97 1130 1 07 1 57 1 46 0 73 1 83 1 71 0 39 2 04 1 90 0 13 2 22 2 06 1175 1 27 1 67 1 56 0 94 1 92 1 79 0 58 2 1...

Page 11: ...0 2 72 2 54 0 11 3 03 2 83 1000 1 20 2 33 2 17 0 93 2 62 2 45 0 65 2 91 2 72 0 35 3 24 3 03 0 16 4 20 3 91 1050 1 42 2 55 2 37 1 14 2 86 2 67 0 85 3 17 2 96 0 62 4 06 3 79 0 39 4 53 4 22 1090 1 63 2 7...

Page 12: ...nd resets at 300 psig 10 3 A Low Pressure Switch Loss Of Charge to protect against loss of refrigerant charge Opens at 7 psig 3 and resets at 22 psig 5 If either one of the above safety controls opens...

Page 13: ...ture indicated in Table 10 It resets automatically The limit switch operates when a high temperature condition caused by inadequate supply air flow occurs thus shutting down the ignition control and c...

Page 14: ...djusting screw on the automatic gas valve Refer to Figure 12 Adjust as follows 1 Remove the cap on the regulator It s located next to the push on electrical terminals 2 To decrease the gas pressure tu...

Page 15: ...tions may require that this balancing be done by someone other than the equipment installer To check the supply air CFM after the initial balancing has been completed 1 Remove the dot plugs from the h...

Page 16: ...dial increment find the cubic feet of gas consumed per hour from Table 12 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible range of the regulato...

Page 17: ...pplied along top of the burner COMBUSTION AIR DISCHARGE Visually inspect discharge outlet periodically to make sure that the buildup of soot and dirt is not excessive If necessary clean to maintain ad...

Page 18: ...osition a The draft motor has inherent protection If the motor shell is hot to the touch wait for the internal overload to reset b If the motor shell is cold with the room thermostat calling for heat...

Page 19: ...pilot burner is aligned properly with the carryover as described in PILOT CHECKOUT b Make sure that the carryovers on adjoining burners are screwed fast and are level with respect to one another 9 Ma...

Page 20: ...10 Code SBY 530 18 N10Y Unitary Products Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rig...

Reviews: