background image

b) Attach two filter guide angles to the inside of each side

plate using 3 screws for each angle. Note the hole
locations on the angles for proper positioning when
attaching them on the side plates. Tighten screws.

c) Attach the two side plates to the center filter support

using 4 screws on each side. Do not tighten screws.

d) Attach the bottom filter support between the side plates

using 2 screws on each side. Do not tighten screws.

e) Attach the hood cover to the side plates using 3 screws

on each side. Do not tighten screws.

f) Set hood assembly on a flat surface to insure all com-

ponents are plumb and now tighten all screws.

3. Attach the hood assembly over the outdoor air opening on

the unit duct panel as follows:

On unit sizes under 10 tons, the flange of the hood cover
must be inserted in under the unit top cover flange. One
screw in the unit cover flange must be removed and one
screw (at the right hand corner of the unit cover flange)
needs only to be loosened to allow the notched flange of
the hood cover to slide into place. Replace and tighten the
2 screws.

On unit sizes 10 ton and over, secure the hood flange to
the duct panel with 3 screws. Use holes in the hood cover
flange as a template and drill 3 holes, 9/64" dia. (#26 drill)
into the duct panel.

On all units, attach the hood side plate flanges to the duct
panel by drilling 6 holes, 9/64" dia. (#26 drill) for each side
plate at the dimples provided in the duct panel. Secure hood
into position using 6 gasketed screws in each side plate.

4. Secure the flange on the hood cover to the duct panel with

3 screws. Use holes in the cover flange as a template and
drill 3 holes, 9/64" dia. (#26 drill) into the duct panel.

5. Insert two (2) 1" filters into the center of the hood, coming

to rest in the center filter support at the back of the hood.
Press filters up against the filter guide angles on the side
plates and use 1 screw (B) on each side of hood to hold
into position.

Insert two (2) 1" filters into the bottom filter support per the
same procedures as the center filters.

NOTE: Install filters so that “Air Flow” arrows point upward,

toward the unit.

ENTHALPY SETPOINT ADJUSTMENT

CAUTION: Extreme care must be exercised in turning both the

setpoint and minimum position adjusting screws to
prevent twisting them off.

6. The enthalpy set point for the dampers may now be set by

selecting the desired setpoint shown in Figure 9. Adjust as
follows:

For a single enthalpy (Model 2EE04700324), carefully
turn the set point adjusting screw to the “A”, “B”, “C” or
“D” setting corresponding to the lettered curve. 

For a dual enthalpy (Model 2EE04700424), carefully
turn the set point adjusting screw fully clockwise past the
“D” setting.

7. To check that the damper blades move smoothly without

binding, carefully turn the minimum position adjusting
screw fully clockwise and then energize and de-energize
terminals “R” to “G”. With terminals “R” to “G” energized,
turn the minimum position screw counterclockwise until the
desired minimum position has been attained.

8. Replace the filter section access panel.

FIG. 8 - ECONOMIZER / MOTORIZED DAMPER RAIN HOOD  ASSEMBLY (OPTION)

530.18-N10Y

Unitary Products Group

7

Summary of Contents for D3CG090

Page 1: ...ting of replacement parts on this equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York Pa 17405 APPROVALS De...

Page 2: ...ication Data 3 2 Gas Heat Application Data 5 3 Pipe Sizing 5 4 Physical Data 8 5 Supply Air Blower Perf 7 1 2 10 Ton 10 6 Supply Air Blower Perf 12 1 2 Ton 11 7 Accessory Static Resistances 11 8 Blowe...

Page 3: ...holes provided in the base rails Spreaders whose length exceeds the largest dimension across the unit MUST be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIB...

Page 4: ...re replaced on the unit to maintain an air tight seal THERMOSTAT The room thermostat should be located on an inside wall approximately 56 above the floor where it will not be subject to drafts sun exp...

Page 5: ...ocal codes or gas company requirements Refer to Table 3 The heating value of the gas may differ with locality The value should be checked with the local gas utility NOTE There may be a local gas utili...

Page 6: ...oad Maintaining proper gas pressure depends on three main factors 1 The vaporization rate which depends on a the temperature of the liquid and b the wetted surface area of the container or containers...

Page 7: ...ing 6 gasketed screws in each side plate 4 Secure the flange on the hood cover to the duct panel with 3 screws Use holes in the cover flange as a template and drill 3 holes 9 64 dia 26 drill into the...

Page 8: ...t 7 8 9 1 10 9 13 4 OUTDOOR FAN Two Per Unit PROPELLER DIA in 24 ea 24 ea 24 ea 24 ea FAN MOTOR HP 1 2 ea 1 2 ea 1 2 ea 3 4 ea NOM CFM TOTAL 2900 ea 3200 ea 3600 ea 4400 ea CONDENSER COIL ROWS DEEP 2...

Page 9: ...R CLEARANCES Front 24 Back 12 Less Economizer 36 With Economizer Left Side Filter Access 24 Less Economizer 54 With Economizer Right Side Cond Coil 24 Below Unit1 20 Above Unit2 72 with 36 maximum Hor...

Page 10: ...9 1 54 1 44 0 04 1 75 1 63 1070 0 86 1 46 1 36 0 54 1 68 1 57 0 20 1 89 1 76 0 04 2 11 1 97 1130 1 07 1 57 1 46 0 73 1 83 1 71 0 39 2 04 1 90 0 13 2 22 2 06 1175 1 27 1 67 1 56 0 94 1 92 1 79 0 58 2 1...

Page 11: ...0 2 72 2 54 0 11 3 03 2 83 1000 1 20 2 33 2 17 0 93 2 62 2 45 0 65 2 91 2 72 0 35 3 24 3 03 0 16 4 20 3 91 1050 1 42 2 55 2 37 1 14 2 86 2 67 0 85 3 17 2 96 0 62 4 06 3 79 0 39 4 53 4 22 1090 1 63 2 7...

Page 12: ...nd resets at 300 psig 10 3 A Low Pressure Switch Loss Of Charge to protect against loss of refrigerant charge Opens at 7 psig 3 and resets at 22 psig 5 If either one of the above safety controls opens...

Page 13: ...ture indicated in Table 10 It resets automatically The limit switch operates when a high temperature condition caused by inadequate supply air flow occurs thus shutting down the ignition control and c...

Page 14: ...djusting screw on the automatic gas valve Refer to Figure 12 Adjust as follows 1 Remove the cap on the regulator It s located next to the push on electrical terminals 2 To decrease the gas pressure tu...

Page 15: ...tions may require that this balancing be done by someone other than the equipment installer To check the supply air CFM after the initial balancing has been completed 1 Remove the dot plugs from the h...

Page 16: ...dial increment find the cubic feet of gas consumed per hour from Table 12 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible range of the regulato...

Page 17: ...pplied along top of the burner COMBUSTION AIR DISCHARGE Visually inspect discharge outlet periodically to make sure that the buildup of soot and dirt is not excessive If necessary clean to maintain ad...

Page 18: ...osition a The draft motor has inherent protection If the motor shell is hot to the touch wait for the internal overload to reset b If the motor shell is cold with the room thermostat calling for heat...

Page 19: ...pilot burner is aligned properly with the carryover as described in PILOT CHECKOUT b Make sure that the carryovers on adjoining burners are screwed fast and are level with respect to one another 9 Ma...

Page 20: ...10 Code SBY 530 18 N10Y Unitary Products Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rig...

Reviews: