background image

OPTIONAL ECONOMIZER / MOTORIZED
DAMPER RAIN HOOD

The following procedure should be used when assembling an
economizer rain hood onto a unit. The outdoor and return air
dampers, the damper actuator, the damper linkage, the outdoor
and return air divider baffles and all the control sensors are
factory mounted as part of the economizer option
All of the hood components, including the filters, the gasketing
and the hardware for assembling are packaged and located
within the unit filter section. (See Figure 8).
1. With filter section access panel removed, take out the hood

components, filters, gasketing and hardware described
above. Remove and discard the outdoor air opening cover
on back of the unit.

2. Assemble the rain hood per the following procedures:

a) Apply gasketing to all hood components as follows:

-To the top outside surface and to the flange (toward
unit) of each side plate. Extend gasketing 1/4" be-
yond the top and bottom of the flange to insure
adequate sealing.

-To the edge and flanges (in one continuous length) on
 each side of the center filter support.

-To the top flange of the bottom filter support (on the
side facing the unit).

-To the hood cover flange (only on unit sizes 10 tons
and over). (No gasketing required on this flange for unit
sizes under 10 tons.)

FIG. 5  - EXTERNAL SUPPLY CONNECTION

EXTERNAL SHUT-OFF

FIG. 6  - BOTTOM SUPPLY CONNECTION

EXTERNAL SHUT-OFF

L.P. UNITS, TANKS AND PIPING

All gas heat units are shipped from the factory equipped for
natural gas use only. The unit may be converted in the field for
use with L.P. / propane gas with accessory kit model number
1NP0421 (U.S.A.) or 1NP0427 (CAN.).

All L.P. / propane gas equipment must conform to the safety
standards of the National Fire Protection Association.

For satisfactory operation, L.P. / propane gas pressure must be
10.5 inch W.C at the unit under full load. Maintaining proper gas
pressure depends on three main factors:

1. The vaporization rate which depends on (a) the temperature

of the liquid and (b) the “wetted surface” area of the container
or containers.

2. The proper pressure regulation. (Two-stage regulation is

recommended from the standpoint of both cost and effi-
ciency.)

3. The pressure drop in the lines between regulators and

between the second stage regulator and the appliance. Pipe
size required will depend on the length of the pipe run and
the total load of all appliances.

Complete information regarding tank sizing for vaporization,
recommended regulator settings, and pipe sizing is available
from most regulator manufacturers and L.P. / propane gas
suppliers.

L.P. / propane gas is an excellent solvent and special pipe
compound must be used when assembling piping for this gas
as it will quickly dissolve white lead or most standard
commercial compounds. Shellac base compounds such as
Rectorseal #5 are satisfactory for this type of gas.

Check all connections for leaks when piping is completed, using
a soap solution. NEVER USE A FLAME.

VENT AND COMBUSTION AIR HOODS

The vent and combustion air hoods (with screens) are shipped
attached to the blower housing in the blower compartment.
These hoods must be installed to assure proper unit function.
Both hoods must be fastened to the outside of the gas heat
access panel with the screws provided in the bag also attached
to the blower housing.
The screen for the combustion air intake hood is secured to the
inside of the access panel opening with three fasteners and the
screws used for mounting the hood to the panel. The top flange
of this hood slips in under the top of the access panel opening
when installing. Refer to Figure 7.

The vent hood is installed by inserting the top flange of the hood
into the slotted opening in the access panel, positioning the vent
screen between the hood flanges and the access panel, and
securing in place.

FIG. 7 - VENT AND COMBUSTION AIR HOODS

530.18-N10Y

6

Unitary Products Group

Summary of Contents for D3CG090

Page 1: ...ting of replacement parts on this equipment All forms referenced in this instruction may be ordered from Publications Distribution Center Unitary Products Group P O Box 1592 York Pa 17405 APPROVALS De...

Page 2: ...ication Data 3 2 Gas Heat Application Data 5 3 Pipe Sizing 5 4 Physical Data 8 5 Supply Air Blower Perf 7 1 2 10 Ton 10 6 Supply Air Blower Perf 12 1 2 Ton 11 7 Accessory Static Resistances 11 8 Blowe...

Page 3: ...holes provided in the base rails Spreaders whose length exceeds the largest dimension across the unit MUST be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIB...

Page 4: ...re replaced on the unit to maintain an air tight seal THERMOSTAT The room thermostat should be located on an inside wall approximately 56 above the floor where it will not be subject to drafts sun exp...

Page 5: ...ocal codes or gas company requirements Refer to Table 3 The heating value of the gas may differ with locality The value should be checked with the local gas utility NOTE There may be a local gas utili...

Page 6: ...oad Maintaining proper gas pressure depends on three main factors 1 The vaporization rate which depends on a the temperature of the liquid and b the wetted surface area of the container or containers...

Page 7: ...ing 6 gasketed screws in each side plate 4 Secure the flange on the hood cover to the duct panel with 3 screws Use holes in the cover flange as a template and drill 3 holes 9 64 dia 26 drill into the...

Page 8: ...t 7 8 9 1 10 9 13 4 OUTDOOR FAN Two Per Unit PROPELLER DIA in 24 ea 24 ea 24 ea 24 ea FAN MOTOR HP 1 2 ea 1 2 ea 1 2 ea 3 4 ea NOM CFM TOTAL 2900 ea 3200 ea 3600 ea 4400 ea CONDENSER COIL ROWS DEEP 2...

Page 9: ...R CLEARANCES Front 24 Back 12 Less Economizer 36 With Economizer Left Side Filter Access 24 Less Economizer 54 With Economizer Right Side Cond Coil 24 Below Unit1 20 Above Unit2 72 with 36 maximum Hor...

Page 10: ...9 1 54 1 44 0 04 1 75 1 63 1070 0 86 1 46 1 36 0 54 1 68 1 57 0 20 1 89 1 76 0 04 2 11 1 97 1130 1 07 1 57 1 46 0 73 1 83 1 71 0 39 2 04 1 90 0 13 2 22 2 06 1175 1 27 1 67 1 56 0 94 1 92 1 79 0 58 2 1...

Page 11: ...0 2 72 2 54 0 11 3 03 2 83 1000 1 20 2 33 2 17 0 93 2 62 2 45 0 65 2 91 2 72 0 35 3 24 3 03 0 16 4 20 3 91 1050 1 42 2 55 2 37 1 14 2 86 2 67 0 85 3 17 2 96 0 62 4 06 3 79 0 39 4 53 4 22 1090 1 63 2 7...

Page 12: ...nd resets at 300 psig 10 3 A Low Pressure Switch Loss Of Charge to protect against loss of refrigerant charge Opens at 7 psig 3 and resets at 22 psig 5 If either one of the above safety controls opens...

Page 13: ...ture indicated in Table 10 It resets automatically The limit switch operates when a high temperature condition caused by inadequate supply air flow occurs thus shutting down the ignition control and c...

Page 14: ...djusting screw on the automatic gas valve Refer to Figure 12 Adjust as follows 1 Remove the cap on the regulator It s located next to the push on electrical terminals 2 To decrease the gas pressure tu...

Page 15: ...tions may require that this balancing be done by someone other than the equipment installer To check the supply air CFM after the initial balancing has been completed 1 Remove the dot plugs from the h...

Page 16: ...dial increment find the cubic feet of gas consumed per hour from Table 12 If the actual input is not within 5 of the furnace rating with allowance being made for the permissible range of the regulato...

Page 17: ...pplied along top of the burner COMBUSTION AIR DISCHARGE Visually inspect discharge outlet periodically to make sure that the buildup of soot and dirt is not excessive If necessary clean to maintain ad...

Page 18: ...osition a The draft motor has inherent protection If the motor shell is hot to the touch wait for the internal overload to reset b If the motor shell is cold with the room thermostat calling for heat...

Page 19: ...pilot burner is aligned properly with the carryover as described in PILOT CHECKOUT b Make sure that the carryovers on adjoining burners are screwed fast and are level with respect to one another 9 Ma...

Page 20: ...10 Code SBY 530 18 N10Y Unitary Products Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rig...

Reviews: