Unitary Products Group

19

036-21311-003-A-0104

BHA

POWER

SUPPLY

COMPRESSOR

OUT-

DOOR

FAN

MOTOR

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

ELECTRIC HEAT ACCESSORY

MINIMUM

CIRCUIT

AMPAC-

ITY

MAX.

FUSE

SIZE

1

AMPS

MAX.

HACR

2

BREAKER

SIZE

MODEL

RLA

LRA

MODEL NO.

ST

AGE

KW

TOTAL

AMPS

036

575-3-60

4.5

32.0

0.4

1.5

2NH04501058
2NH04501558

1
1

10.0  ***
15.0  ***

9.6

14.4

19.6
25.6

20
30

20
30

042

575-3-60

5.8

44.0

0.4

1.5

2NH04501058
2NH04501558

1
1

10.0  ***
15.0  ***

9.6

14.4

21.1
27.2

25
30

25
30

048

575-3-60

5.6

44.0

0.6

1.6

2NH04501058
2NH04501558
2NH04502058
2NH04502558

1
1
2
2

10.0  ***
15.0  ***
20.0  ***
25.0  ***

9.6

14.4
19.2
24.1

21.3
27.3
33.3
39.3

25
30
35
40

25
30
35

40

060

575-3-60

6.4

50.0

0.6

2.8

2NH04501058
2NH04501558
2NP04502058
2NP04502558

1
1
2
2

10.0  ***
15.0  ***
20.0  ***
25.0  ***

9.6

14.4
19.2
24.1

23.4
29.5
35.5
41.5

25
30
40
45

25
30
40
45

1

= Dual element, time delay type.                                                                                                                            * = KW listed is for 240 volts, use table at top of page for 208 or 230 volts.

2

= Standard circuit breakers may be used in Canada and on applications                                                            ** = KW listed is for 480 volts, use table at top of page for 460 volts.

over 60 amps where the heaters are separately fused.

*** = KW listed is for 600 volts, use table at top of page for 575 volts.

ELECTRIC HEAT

CORRECTION

FACTORS

NOMINAL VOLTAGE

VOLTAGE

KW CAP. MULTI-

PLIER

240

208
230

.75
.92

480

460

.92

600

575

.92

ELECTRICAL DATA

(HEAT PUMP / ELECTRIC HEAT) (CONTINUED)

Summary of Contents for Champion Series

Page 1: ...currents air velocity and temperature and unit vibration are monitored and recorded by the system to insure unit performance Equal size side supply and return duct connections allows easy hook up of d...

Page 2: ...o aids in sound alterations with it s Super Structure design This design strategically places embossments in the pan for optimum strength and rigidity FAN SYSTEM All models operate over a wide range o...

Page 3: ...sup ply and one return air rectangle to round duct adapter Adapters are preformed and designed to fit over current duct openings on the base unit Transition is from 15 square to 14 round ROOF CURBS NR...

Page 4: ...annual usage period for cooling divided by the total electric power input in watt hours during the same period COP Coefficient of Performance the total heating capacity provided by the refrigeration...

Page 5: ...2 23 2 16 2 11 2 12 Sensible Capacity MBH 1 Entering Dry Bulb F 86 10 9 13 4 13 9 13 8 12 3 14 8 14 4 14 3 13 6 16 3 14 9 14 8 14 9 17 1 15 3 15 2 16 2 17 9 15 7 15 6 83 9 6 12 1 13 6 13 5 10 7 13 5...

Page 6: ...4 Sensible Capacity MBH 1 Entering Dry Bulb F 86 13 9 17 3 17 9 17 9 15 5 18 8 18 5 18 4 17 1 20 3 19 1 19 0 18 6 21 0 19 4 19 4 20 1 21 6 19 8 19 8 83 12 2 15 6 17 6 17 6 13 5 17 3 18 4 18 3 14 8 19...

Page 7: ...Capacity MBH 1 Entering Dry Bulb F 86 17 6 21 9 22 5 22 6 19 5 23 6 23 0 23 0 21 5 25 3 23 5 23 5 23 5 26 1 23 9 24 0 25 5 26 9 24 4 24 4 83 15 5 19 8 22 2 22 3 17 0 21 7 22 8 22 9 18 5 23 5 23 5 23 5...

Page 8: ...Entering Dry Bulb F 86 21 0 25 8 25 1 23 7 23 9 28 4 27 0 25 5 26 9 31 1 28 8 27 2 29 5 32 9 30 0 28 3 32 1 34 6 31 2 29 5 83 18 5 23 2 25 1 23 7 20 9 26 2 27 0 25 5 23 4 29 3 28 8 27 2 25 5 31 3 30...

Page 9: ...H 1 Entering Dry Bulb F 86 23 4 29 0 27 9 25 3 26 5 31 9 30 1 27 3 29 6 34 8 32 3 29 3 32 0 35 8 32 7 29 7 34 4 36 9 33 1 30 1 83 20 4 26 0 27 9 25 3 23 0 29 2 30 1 27 3 25 5 32 3 32 3 29 3 27 3 33 9...

Page 10: ...lb F 86 28 3 35 7 38 8 36 8 31 6 39 3 40 0 38 0 34 9 43 0 41 3 39 2 38 2 44 7 42 1 40 0 41 4 46 5 43 0 40 9 83 24 8 32 3 36 9 36 0 27 5 35 7 39 1 37 6 30 2 39 1 41 3 39 2 32 8 42 0 42 1 40 0 35 4 44 8...

Page 11: ...5 44 3 46 6 45 4 38 4 48 2 47 8 46 5 42 3 52 2 48 9 47 6 43 7 53 1 49 6 48 3 45 1 54 1 50 3 48 9 83 30 3 40 0 45 7 44 6 33 4 44 1 47 3 46 1 36 5 48 1 48 9 47 6 37 5 49 3 49 6 48 3 38 5 50 6 50 3 48 9...

Page 12: ...2 543 15 457 19 060 23 517 29 028 KW 1 428 1 581 1 733 1 886 2 038 2 190 2 343 2 495 1 These capacities are net capacities the indoor motor heat has been added These power inputs are total power input...

Page 13: ...2 25 624 30 154 35 507 41 834 KW 2 566 2 694 2 822 2 950 3 078 3 206 3 335 3 463 1 These capacities are net capacities the indoor motor heat has been added These power inputs are total power inputs th...

Page 14: ...ities the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added HEATING CAPACITIES 4 TON BHA048 CFM RETURN AIR CAP1 OUTDOOR AIR TEMPERATURE...

Page 15: ...N DATA MODEL BHA 018 024 030 036 042 048 060 MINIMUM AIR FLOW CFM COOLING 450 600 750 900 1 050 1 200 1 500 HEATING 450 600 750 900 1 050 1 200 1 500 MAXIMUM AIR FLOW CFM COOLING 750 1 000 1 250 1 500...

Page 16: ...788 691 1739 1652 1528 940 752 677 NOTE Above data includes allowances for a dry indoor coil and no filters For additional pressure drops refer to the Additional Static Pressure Resistance table MODEL...

Page 17: ...253 11 2 60 0 1 1 2 6 17 7 25 25 96 40 030 208 230 1 60 187 253 12 0 73 0 1 1 2 6 18 7 25 25 96 40 036 208 230 1 60 187 253 17 3 94 0 1 1 3 5 26 2 35 35 96 40 042 208 230 1 60 187 253 20 5 120 0 1 1 3...

Page 18: ...88 1 103 7 114 1 126 3 140 2 148 8 166 2 90 100 110 125 150 150 150 175 90 100 110 125 150 150 150 175 060 208 230 1 60 28 9 165 0 1 5 7 0 2NH04501006 2NH04501506 2NH04502006 2NH04502506 2 2 2 2 7 5...

Page 19: ...25 0 9 6 14 4 19 2 24 1 21 3 27 3 33 3 39 3 25 30 35 40 25 30 35 40 060 575 3 60 6 4 50 0 0 6 2 8 2NH04501058 2NH04501558 2NP04502058 2NP04502558 1 1 2 2 10 0 15 0 20 0 25 0 9 6 14 4 19 2 24 1 23 4 2...

Page 20: ...LTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 131 32 DIA KNOCKOUT FRONT ELECTRICAL FILTER SERVICE ACCESS COMPARTMENT PANEL OVERALL OVERALL 4 1 2 11 2 2 1 2 All dimensions are in inches They are subjec...

Page 21: ...S THEREAFTER FOR ALL OTHER HEATERS ZERO INCH CLEARANCE ALL SIDES FOR ENTIRE LENGTH OF DUCT FLEXIBLE DUCT COLLAR NOTE FOR UNITS APPLIED WITH A ROOF CURB THE MINIMUM CLEARANCE MAY BE REDUCED FROM 1 INCH...

Page 22: ...FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT ROOF CURB INSTALLATION REAR DUCT SLAB ON GROUND INSTALLATION ROOF CURB INSTALLATION BOTTOM DUCT TYPICAL ROO...

Page 23: ...F CURB DIMENSIONS 8 roof curb also available UNIT BASE RAIL UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FRAME COUNTERFLASHING INSULATION CANT STRIP ROOF DECK AND ROOFING MATERIAL INSULATION A...

Page 24: ...PR 708 PR 716 PR 716 PR 713 PR 713 PR 710 PR 710 PR F6 F6 F4 F4 F2 F2 K6 K6 K4 K4 K5 K5 K3 K3 M1 M1 714 BK 714 BK 706 BK 706 BK 711 BK 711 BK 703 BK 703 BK 709 BK 709 BK F1 F1 F3 F3 F5 F5 DUAL POINT E...

Page 25: ...ts Group 25 036 21311 003 A 0104 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY M R C COMPR RELAY DFST STAT M1 DETAIL A 222 Y BLU BLU DS DEFROST CONTROL 031 01268 000B FOR DEFROST CONTROL 031 09104 000A...

Page 26: ...R 2 1 2 R C T 1 1 0 9 B K 2 4 V 1 0 8 P R 4 8 0 O R 6 0 0 2 1 4 B R 8 D 7 E A B K 3 8 1 3 B R 8 1 4 Y L 2 L 2 L 2 1 2 3 H 1 L 1 L 1 L 1 K 1 2 0 9 R K 2 F A N C O N T R O L B O A R D T L H F L H 4 1 2...

Page 27: ...FAN MOTOR K2 RELAY ELECTRIC HEATER K3 RELAY ELECTRIC HEATER 24V DC COIL K7 RELAY LIMIT TRIP 24V DC COIL LP LOW PRESSURE SWITCH OPTIONAL ACCESSORY OPEN 7 PSIG LS LIMIT SWITCH ELECTRIC HEAT PART OF ELEC...

Page 28: ...uilding structure duct work and base unit 10 Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPTI copper ridged mount connection INDOOR SUPPLY FA...

Page 29: ...tion with nickel chromium ele ments shall be provided in a range of 5 thru 25 KW offer ing two stages of capacity 7 KW and above on single phase heaters and one 20 KW and above on three phase heaters...

Page 30: ...30 Unitary Products Group 036 21311 003 A 0104...

Page 31: ...Unitary Products Group 31 036 21311 003 A 0104...

Page 32: ...Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2004 All Rights Reserved 036 21311 003 A 0104 Supersedes 036...

Reviews: