Unitary Products Group

15

036-21311-003-A-0104

HEATING CAPACITIES -

5 TON (BHA060)

CFM

RETURN AIR

CAP

1

OUTDOOR AIR TEMPERATURE,

°

F (72% RH)

°

F

&  KW

-10

0

10

20

30

40

50

60

1,500

55

MBH

19.316

23.261

27.902

33.364

39.79

47.351

56.247

66.714

KW

3.57

3.829

4.088

4.347

4.606

4.865

5.124

5.383

70

MBH

18.491

22.436

27.077

32.539

38.965

46.526

55.422

65.889

KW

4.061

4.32

4.579

4.838

5.097

5.356

5.615

5.874

80

MBH

15.362

19.307

23.948

29.41

35.836

43.397

52.293

62.76

KW

4.358

4.617

4.876

5.135

5.394

5.653

5.912

6.171

2,000

55

MBH

23.164

27.109

31.75

37.212

43.638

51.199

60.095

70.562

KW

3.624

3.883

4.142

4.401

4.66

4.919

5.178

5.437

70

MBH

22.339

26.284

30.925

36.387

42.813

50.374

59.27

69.737

KW

4.115

4.374

4.633

4.892

5.151

5.41

5.669

5.928

80

MBH

19.21

23.155

27.796

33.258

39.684

47.245

56.141

66.608

KW

4.412

4.671

4.93

5.189

5.448

5.707

5.966

6.225

2,500

55

MBH

24.796

28.741

33.382

38.844

45.27

52.831

61.727

72.194

KW

3.754

4.013

4.272

4.531

4.79

5.049

5.308

5.567

70

MBH

23.971

27.916

32.557

38.019

44.445

52.006

60.902

71.369

KW

4.245

4.504

4.763

5.022

5.281

5.54

5.799

6.058

80

MBH

20.842

24.787

29.428

34.89

41.316

48.877

57.773

68.24

KW

4.542

4.801

5.06

5.319

5.578

5.837

6.096

6.355

APPLICATION DATA

MODEL

BHA

018

024

030

036

042

048

060

MINIMUM AIR FLOW

(CFM)

COOLING

450

600

750

900

1,050

1,200

1,500

HEATING

450

600

750

900

1,050

1,200

1,500

MAXIMUM AIR FLOW

(CFM)

COOLING

750

1,000

1,250

1,500

1,750

2,000

2,500

HEATING

750

1,000

1,250

1,500

1,750

2,000

2,500

MINIMUM OPERATING TEMPERATURE IN COOLING MODE

(AMBIENT,

°

F)

45

45

45

45

45

45

45

MINIMUM MIXED AIR IN COOLING MODE

(RETURN AIR, DB

°

F/WB

°

F)

68 / 57

68 / 57

68 / 57

68 / 57

68 / 57

68 / 57

68 / 57

MINIMUM MIXED AIR IN HEATING MODE

(RETURN AIR,

°

F)

55

55

55

55

55

55

55

ADDITIONAL STATIC PRESSURE RESISTANCE

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000

Wet Indoor coil

0.01

0.01

0.01

0.02

0.02

0.03

0.03

0.04

0.04

0.04

0.04

0.04

0.05

0.05

0.06

0.07

Economizer

0.00

0.00

0.00

0.01

0.01

0.01

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.08

Filter/Frame Kit

0.01

0.02

0.02

0.02

0.02

0.02

0.03

0.03

0.03

0.03

0.04

0.05

0.05

0.06

0.06

0.07

Electric Heat

0.02

0.03

0.03

0.03

0.04

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.01

0.11

0.11

0.12

NOTE: 1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2. The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver

less CFM during full economizer operation.

Summary of Contents for Champion Series

Page 1: ...currents air velocity and temperature and unit vibration are monitored and recorded by the system to insure unit performance Equal size side supply and return duct connections allows easy hook up of d...

Page 2: ...o aids in sound alterations with it s Super Structure design This design strategically places embossments in the pan for optimum strength and rigidity FAN SYSTEM All models operate over a wide range o...

Page 3: ...sup ply and one return air rectangle to round duct adapter Adapters are preformed and designed to fit over current duct openings on the base unit Transition is from 15 square to 14 round ROOF CURBS NR...

Page 4: ...annual usage period for cooling divided by the total electric power input in watt hours during the same period COP Coefficient of Performance the total heating capacity provided by the refrigeration...

Page 5: ...2 23 2 16 2 11 2 12 Sensible Capacity MBH 1 Entering Dry Bulb F 86 10 9 13 4 13 9 13 8 12 3 14 8 14 4 14 3 13 6 16 3 14 9 14 8 14 9 17 1 15 3 15 2 16 2 17 9 15 7 15 6 83 9 6 12 1 13 6 13 5 10 7 13 5...

Page 6: ...4 Sensible Capacity MBH 1 Entering Dry Bulb F 86 13 9 17 3 17 9 17 9 15 5 18 8 18 5 18 4 17 1 20 3 19 1 19 0 18 6 21 0 19 4 19 4 20 1 21 6 19 8 19 8 83 12 2 15 6 17 6 17 6 13 5 17 3 18 4 18 3 14 8 19...

Page 7: ...Capacity MBH 1 Entering Dry Bulb F 86 17 6 21 9 22 5 22 6 19 5 23 6 23 0 23 0 21 5 25 3 23 5 23 5 23 5 26 1 23 9 24 0 25 5 26 9 24 4 24 4 83 15 5 19 8 22 2 22 3 17 0 21 7 22 8 22 9 18 5 23 5 23 5 23 5...

Page 8: ...Entering Dry Bulb F 86 21 0 25 8 25 1 23 7 23 9 28 4 27 0 25 5 26 9 31 1 28 8 27 2 29 5 32 9 30 0 28 3 32 1 34 6 31 2 29 5 83 18 5 23 2 25 1 23 7 20 9 26 2 27 0 25 5 23 4 29 3 28 8 27 2 25 5 31 3 30...

Page 9: ...H 1 Entering Dry Bulb F 86 23 4 29 0 27 9 25 3 26 5 31 9 30 1 27 3 29 6 34 8 32 3 29 3 32 0 35 8 32 7 29 7 34 4 36 9 33 1 30 1 83 20 4 26 0 27 9 25 3 23 0 29 2 30 1 27 3 25 5 32 3 32 3 29 3 27 3 33 9...

Page 10: ...lb F 86 28 3 35 7 38 8 36 8 31 6 39 3 40 0 38 0 34 9 43 0 41 3 39 2 38 2 44 7 42 1 40 0 41 4 46 5 43 0 40 9 83 24 8 32 3 36 9 36 0 27 5 35 7 39 1 37 6 30 2 39 1 41 3 39 2 32 8 42 0 42 1 40 0 35 4 44 8...

Page 11: ...5 44 3 46 6 45 4 38 4 48 2 47 8 46 5 42 3 52 2 48 9 47 6 43 7 53 1 49 6 48 3 45 1 54 1 50 3 48 9 83 30 3 40 0 45 7 44 6 33 4 44 1 47 3 46 1 36 5 48 1 48 9 47 6 37 5 49 3 49 6 48 3 38 5 50 6 50 3 48 9...

Page 12: ...2 543 15 457 19 060 23 517 29 028 KW 1 428 1 581 1 733 1 886 2 038 2 190 2 343 2 495 1 These capacities are net capacities the indoor motor heat has been added These power inputs are total power input...

Page 13: ...2 25 624 30 154 35 507 41 834 KW 2 566 2 694 2 822 2 950 3 078 3 206 3 335 3 463 1 These capacities are net capacities the indoor motor heat has been added These power inputs are total power inputs th...

Page 14: ...ities the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added HEATING CAPACITIES 4 TON BHA048 CFM RETURN AIR CAP1 OUTDOOR AIR TEMPERATURE...

Page 15: ...N DATA MODEL BHA 018 024 030 036 042 048 060 MINIMUM AIR FLOW CFM COOLING 450 600 750 900 1 050 1 200 1 500 HEATING 450 600 750 900 1 050 1 200 1 500 MAXIMUM AIR FLOW CFM COOLING 750 1 000 1 250 1 500...

Page 16: ...788 691 1739 1652 1528 940 752 677 NOTE Above data includes allowances for a dry indoor coil and no filters For additional pressure drops refer to the Additional Static Pressure Resistance table MODEL...

Page 17: ...253 11 2 60 0 1 1 2 6 17 7 25 25 96 40 030 208 230 1 60 187 253 12 0 73 0 1 1 2 6 18 7 25 25 96 40 036 208 230 1 60 187 253 17 3 94 0 1 1 3 5 26 2 35 35 96 40 042 208 230 1 60 187 253 20 5 120 0 1 1 3...

Page 18: ...88 1 103 7 114 1 126 3 140 2 148 8 166 2 90 100 110 125 150 150 150 175 90 100 110 125 150 150 150 175 060 208 230 1 60 28 9 165 0 1 5 7 0 2NH04501006 2NH04501506 2NH04502006 2NH04502506 2 2 2 2 7 5...

Page 19: ...25 0 9 6 14 4 19 2 24 1 21 3 27 3 33 3 39 3 25 30 35 40 25 30 35 40 060 575 3 60 6 4 50 0 0 6 2 8 2NH04501058 2NH04501558 2NP04502058 2NP04502558 1 1 2 2 10 0 15 0 20 0 25 0 9 6 14 4 19 2 24 1 23 4 2...

Page 20: ...LTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 131 32 DIA KNOCKOUT FRONT ELECTRICAL FILTER SERVICE ACCESS COMPARTMENT PANEL OVERALL OVERALL 4 1 2 11 2 2 1 2 All dimensions are in inches They are subjec...

Page 21: ...S THEREAFTER FOR ALL OTHER HEATERS ZERO INCH CLEARANCE ALL SIDES FOR ENTIRE LENGTH OF DUCT FLEXIBLE DUCT COLLAR NOTE FOR UNITS APPLIED WITH A ROOF CURB THE MINIMUM CLEARANCE MAY BE REDUCED FROM 1 INCH...

Page 22: ...FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT ROOF CURB INSTALLATION REAR DUCT SLAB ON GROUND INSTALLATION ROOF CURB INSTALLATION BOTTOM DUCT TYPICAL ROO...

Page 23: ...F CURB DIMENSIONS 8 roof curb also available UNIT BASE RAIL UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FRAME COUNTERFLASHING INSULATION CANT STRIP ROOF DECK AND ROOFING MATERIAL INSULATION A...

Page 24: ...PR 708 PR 716 PR 716 PR 713 PR 713 PR 710 PR 710 PR F6 F6 F4 F4 F2 F2 K6 K6 K4 K4 K5 K5 K3 K3 M1 M1 714 BK 714 BK 706 BK 706 BK 711 BK 711 BK 703 BK 703 BK 709 BK 709 BK F1 F1 F3 F3 F5 F5 DUAL POINT E...

Page 25: ...ts Group 25 036 21311 003 A 0104 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY M R C COMPR RELAY DFST STAT M1 DETAIL A 222 Y BLU BLU DS DEFROST CONTROL 031 01268 000B FOR DEFROST CONTROL 031 09104 000A...

Page 26: ...R 2 1 2 R C T 1 1 0 9 B K 2 4 V 1 0 8 P R 4 8 0 O R 6 0 0 2 1 4 B R 8 D 7 E A B K 3 8 1 3 B R 8 1 4 Y L 2 L 2 L 2 1 2 3 H 1 L 1 L 1 L 1 K 1 2 0 9 R K 2 F A N C O N T R O L B O A R D T L H F L H 4 1 2...

Page 27: ...FAN MOTOR K2 RELAY ELECTRIC HEATER K3 RELAY ELECTRIC HEATER 24V DC COIL K7 RELAY LIMIT TRIP 24V DC COIL LP LOW PRESSURE SWITCH OPTIONAL ACCESSORY OPEN 7 PSIG LS LIMIT SWITCH ELECTRIC HEAT PART OF ELEC...

Page 28: ...uilding structure duct work and base unit 10 Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPTI copper ridged mount connection INDOOR SUPPLY FA...

Page 29: ...tion with nickel chromium ele ments shall be provided in a range of 5 thru 25 KW offer ing two stages of capacity 7 KW and above on single phase heaters and one 20 KW and above on three phase heaters...

Page 30: ...30 Unitary Products Group 036 21311 003 A 0104...

Page 31: ...Unitary Products Group 31 036 21311 003 A 0104...

Page 32: ...Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2004 All Rights Reserved 036 21311 003 A 0104 Supersedes 036...

Reviews: