Unitary Products Group
15
036-21311-003-A-0104
HEATING CAPACITIES -
5 TON (BHA060)
CFM
RETURN AIR
CAP
1
OUTDOOR AIR TEMPERATURE,
°
F (72% RH)
°
F
& KW
-10
0
10
20
30
40
50
60
1,500
55
MBH
19.316
23.261
27.902
33.364
39.79
47.351
56.247
66.714
KW
3.57
3.829
4.088
4.347
4.606
4.865
5.124
5.383
70
MBH
18.491
22.436
27.077
32.539
38.965
46.526
55.422
65.889
KW
4.061
4.32
4.579
4.838
5.097
5.356
5.615
5.874
80
MBH
15.362
19.307
23.948
29.41
35.836
43.397
52.293
62.76
KW
4.358
4.617
4.876
5.135
5.394
5.653
5.912
6.171
2,000
55
MBH
23.164
27.109
31.75
37.212
43.638
51.199
60.095
70.562
KW
3.624
3.883
4.142
4.401
4.66
4.919
5.178
5.437
70
MBH
22.339
26.284
30.925
36.387
42.813
50.374
59.27
69.737
KW
4.115
4.374
4.633
4.892
5.151
5.41
5.669
5.928
80
MBH
19.21
23.155
27.796
33.258
39.684
47.245
56.141
66.608
KW
4.412
4.671
4.93
5.189
5.448
5.707
5.966
6.225
2,500
55
MBH
24.796
28.741
33.382
38.844
45.27
52.831
61.727
72.194
KW
3.754
4.013
4.272
4.531
4.79
5.049
5.308
5.567
70
MBH
23.971
27.916
32.557
38.019
44.445
52.006
60.902
71.369
KW
4.245
4.504
4.763
5.022
5.281
5.54
5.799
6.058
80
MBH
20.842
24.787
29.428
34.89
41.316
48.877
57.773
68.24
KW
4.542
4.801
5.06
5.319
5.578
5.837
6.096
6.355
APPLICATION DATA
MODEL
BHA
018
024
030
036
042
048
060
MINIMUM AIR FLOW
(CFM)
COOLING
450
600
750
900
1,050
1,200
1,500
HEATING
450
600
750
900
1,050
1,200
1,500
MAXIMUM AIR FLOW
(CFM)
COOLING
750
1,000
1,250
1,500
1,750
2,000
2,500
HEATING
750
1,000
1,250
1,500
1,750
2,000
2,500
MINIMUM OPERATING TEMPERATURE IN COOLING MODE
(AMBIENT,
°
F)
45
45
45
45
45
45
45
MINIMUM MIXED AIR IN COOLING MODE
(RETURN AIR, DB
°
F/WB
°
F)
68 / 57
68 / 57
68 / 57
68 / 57
68 / 57
68 / 57
68 / 57
MINIMUM MIXED AIR IN HEATING MODE
(RETURN AIR,
°
F)
55
55
55
55
55
55
55
ADDITIONAL STATIC PRESSURE RESISTANCE
DESCRIPTION
RESISTANCE, IWG
CFM
500
600
700
800
900
1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000
Wet Indoor coil
0.01
0.01
0.01
0.02
0.02
0.03
0.03
0.04
0.04
0.04
0.04
0.04
0.05
0.05
0.06
0.07
Economizer
0.00
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.08
Filter/Frame Kit
0.01
0.02
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.05
0.05
0.06
0.06
0.07
Electric Heat
0.02
0.03
0.03
0.03
0.04
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.01
0.11
0.11
0.12
NOTE: 1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
2. The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver
less CFM during full economizer operation.