18
Unitary Products Group
036-21311-003-A-0104
BHA
POWER
SUPPLY
COMPRESSOR OUTDOOR
FAN
MOTOR
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
ELECTRIC HEAT ACCESSORY
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
1
AMPS
MAX.
HACR
2
BREAKER
SIZE
MODEL
RLA
LRA
MODEL NO.
ST
AGE
KW
TOTAL
AMPS
018 208/230-1-60
9.0
48.0
1.1
2.6
2NH04500506
2NH04500706
1
2
3.8/5.0 *
5.6/7.5 *
18.1/20.8
27.1/31.3
37.5/41.0
48.8/54.0
40/45
50/60
40/45
50/60
024 208/230-1-60
11.2
60.0
1.1
2.6
2NH04500506
2NH04500706
2NH04501006
1
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
18.1/20.8
27.1/31.3
36.1/41.7
40.7/44.2
52.0/57.2
63.3/70.2
45/50
60/60
70/80
45/50
60/60
70/80
030 208/230-1-60
14.7
73.0
1.1
2.6
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.3/31.3
36.1/41.7
54.2/62.5
44.7/48.2
56.0/61.2
67.3/74.2
89.8/100.3
50/50
60/70
70/80
90/110
50/50
60/70
70/80
90/110
14.7
73.0
1.1
2.6
2ND04501506
2
3.8/5.0
18.1/20.8
44.7/48.2
50/50
50/50
0.0
0.0
0.0
0.0
7.5/10.0
36.1/41.7
45.1/52.1
50/60
50/60
036 208/230-1-60
17.3
94.0
1.1
3.5
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.1/31.3
36.1/41.7
54.2/62.5
48.8/52.3
60.1/65.3
71.4/78.3
93.9/104.4
60/60
70/70
80/80
100/110
60/60
70/70
80/80
100/110
17.3
94.0
1.1
3.5
2ND04501506
2
3.8/5.0
18.1/20.8
48.8/52.3
60/60
60/60
0.0
0.0
0.0
0.0
7.5/10.0
36.1/41.7
45.1/52.1
50/60
50/60
042 208/230-1-60
20.5
120.0
1.1
3.5
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.1/31.3
36.1/41.7
54.2/62.5
52.8/56.3
64.1/69.3
75.4/82.3
97.9/108.4
60/70
70/80
80/90
100/110
60/70
70/80
80/90
100/110
20.5
120.0
1.1
3.5
2ND04501506
2
3.8/5.0
18.1/20.8
52.8/56.3
60/70
60/70
0.0
0.0
0.0
0.0
7.5/10.0
36.1/41.7
45.1/52.1
50/60
50/60
048 208/230-1-60
24.4
140.0
1.5
4.0
2NP04501006
2NP04501506
2NP04502006
2NX04502506
2
2
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
36.1/41.7
54.2/62.5
72.2/83.3
90.3/104.2
81.1/88.1
103.7/114.1
126.3/140.2
148.8/166.2
90/100
110/125
150/150
150/175
90/100
110/125
150/150
150/175
060 208/230-1-60
28.9
165.0
1.5
7.0
2NH04501006
2NH04501506
2NH04502006
2NH04502506
2
2
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
36.1/41.7
54.2/62.5
72.2/83.3
90.3/104.2
89.8/96.7
112.3/122.8
134.9/148.8
157.5/174.8
100/110
125/125
150/150
175/175
100/110
125/125
150/150
175/175
036 208/230-3-60
10.9
78.0
1.1
3.5
2NH04501025
2NH04501525
1
1
7.5/10.0 *
11.3/15.0 *
20.8/24.1
31.3/36.1
44.3/48.3
57.3/63.3
45/50
60/70
45/50
60/70
042 208/230-3-60
14.1
110.0
1.1
3.5
2NH04501025
2NH04501525
1
1
7.5/10.0 *
11.3/15.0 *
20.8/24.1
31.3/36.1
48.3/57.3
61.3/67.3
50/60
70/70
50/60
70/70
048 208/230-3-60
14.1
105.0
1.5
4.0
2NP04501025
2NP04501525
2NP04502025
2NH04502525
1
1
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
20.8/24.1
31.3/36.1
41.7/48.1
52.1/60.1
49.2/53.2
62.2/68.2
75.3/83.3
88.3/98.3
50/60
70/70
80/90
90/100
50/60
70/70
80/90
90/100
060 208/230-3-60
16.0
125.0
1.5
7.0
2NH04501025
2NH04501525
2NH04502025
2NH04502525
1
1
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
20.8/24.1
31.3/36.1
41.7/48.1
52.1/60.1
54.6/58.6
67.6/73.6
80.7/88.7
93.7/103.7
60/60
70/80
90/90
100/110
60/60
70/80
90/90
100/110
036
460-3-60
5.8
40.0
0.6
1.8
2NH04501046
2NH04501546
1
1
10.0 **
15.0 **
12.8
18.0
24.6
32.2
25
35
25
35
042
460-3-60
7.1
54.0
0.6
1.8
2NH04501046
2NH04501546
1
1
10.0 **
15.0 **
12.0
18.0
26.2
33.8
30
35
30
35
048
460-3-60
7.1
55.0
0.8
2.0
2NP04501046
2NH04501546
2NH04502046
2NH04502546
1
1
2
2
10.0 **
15.0 **
20.0 **
25.0 **
12.0
18.0
24.1
30.1
26.7
34.2
41.7
49.3
30
35
45
50
30
35
45
50
060
460-3-60
8.0
67.0
0.8
3.5
2NH04501046
2NH04501546
2NP04502046
2NP04502546
1
1
2
2
10.0 **
15.0 **
20.0 **
25.0 **
12.0
18.0
24.1
30.1
29.4
36.9
44.4
51.9
30
40
45
60
30
40
45
60
1
= Dual element, time delay type. * = KW listed is for 240 volts, use table at top of page for 208 or 230 volts.
2
= Standard circuit breakers may be used in Canada and on applications ** = KW listed is for 480 volts, use table at top of page for 460 volts.
over 60 amps where the heaters are separately fused. *** = KW listed is for 600 volts, use table at top of page for 575 volts.
ELECTRICAL DATA
(HEAT PUMP / ELECTRIC HEAT)