Unitary Products Group
17
036-21311-003-A-0104
FIELD WIRING DIAGRAM
ELECTRICAL DATA
(BASIC UNIT)
REFER TO ELECTRICAL DATA
TABLES TO SIZE THE DIS-
CONNECT
REFER TO ELECTRICAL DATA
TABLES TO SIZE THE DIS-
CONNECT
POWER WIRING
R
G
W
R
C
Y
Y
W 2
C
W 1
O
O
G
24 VOLT TRANSFORMER
UNIT TERMINAL STRIP
THERMOSTAT
NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.25
AMPS FOR ALL MODELS.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation. Verify proper operation after servicing.
PROGRAMMABLE
THERMOSTAT ONLY
** = Minimum wire size of 18 AWG
wire should be used for all field
installed 24 volt wire.
**
* = Only required on units with
supplemental electric heat.
*
CONTROL WIRING
MODEL
BHA
POWER SUP-
PLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
OUTDOOR
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
018
208/230-1-60
187
253
9.0
48.0
1.1
2.6
14.9
20
20
.96
40
024
208/230-1-60
187
253
11.2
60.0
1.1
2.6
17.7
25
25
.96
40
030
208/230-1-60
187
253
12.0
73.0
1.1
2.6
18.7
25
25
.96
40
036
208/230-1-60
187
253
17.3
94.0
1.1
3.5
26.2
35
35
.96
40
042
208/230-1-60
187
253
20.5
120.0
1.1
3.5
30.2
40
40
.96
40
048
208/230-1-60
187
253
24.4
140.0
1.5
4.0
36.0
50
50
.96
40
060
208/230-1-60
187
253
28.9
165.0
1.5
7.0
44.6
60
60
.96
40
036
208/230-3-60
187
253
10.9
78.0
1.1
3.5
18.2
25
25
.96
75
042
208/230-3-60
187
253
14.1
110.0
1.1
3.5
22.2
30
30
.96
75
048
208/230-3-60
187
253
14.1
105.0
1.5
4.0
23.1
30
30
.96
75
060
208/230-3-60
187
253
16.0
125.0
1.5
7.0
28.5
40
40
.96
75
036
460-3-60
414
504
5.8
40.0
0.6
1.8
9.6
15
15
.96
75
042
460-3-60
414
504
7.1
54.0
0.6
1.8
11.2
15
15
.96
75
048
460-3-60
414
504
7.1
55.0
0.8
2.0
11.7
15
15
.96
75
060
460-3-60
414
504
8.0
67.0
0.8
3.5
14.3
20
20
.96
75
036
575-3-60
518
630
4.5
32.0
0.4
1.5
7.6
15
15
.96
75
042
575-3-60
518
630
5.8
44.0
0.4
1.5
9.1
15
15
.96
75
048
575-3-60
518
630
5.6
44.0
0.6
1.6
9.3
15
15
.96
75
060
575-3-60
518
630
6.4
50.0
0.6
2.8
11.4
15
15
.96
75
1
= Rated in accordance with ARI Standard 110, utilization range “A”.
2
= Dual element, time delay type.
ELECTRIC HEAT
CORRECTION
FACTORS
NOMINAL VOLTAGE
VOLTAGE
KW CAP. MULTI-
PLIER
240
208
230
.75
.92
480
460
.92
600
575
.92