PERFORMANCE DATA - 5 TON
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °
F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTICE
Outdoor units must be applied with Johnson Controls Unitary Products indoor coils, so Condenser Only data is not provided.
COOLING PERFORMANCE DATA - HIGH
AIR CONDITIONER MODEL NO.
YXV60B21S
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
IDCFM
1530
1800
1980
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
55
T.C.
51.3
53.7
54.6
58.4
59.8
52.9
55.0
55.6
58.6
59.6
54.4
56.3
56.5
58.7
59.4
S.C.
34.7
35.5
35.7
39.4
40.2
36.0
36.8
36.9
39.6
40.1
37.3
38.0
38.0
39.7
40.0
KW
2.60
2.58
2.58
2.56
2.54
2.67
2.66
2.66
2.63
2.62
2.74
2.73
2.73
2.71
2.70
65
T.C.
51.3
53.8
54.6
58.9
62.7
53.0
55.1
55.6
59.5
62.9
54.7
56.4
56.6
60.2
63.1
S.C.
34.7
36.1
36.3
40.1
42.4
36.1
37.2
37.3
40.5
42.6
37.5
38.2
38.3
41.0
42.8
KW
3.13
3.13
3.13
3.13
3.13
3.21
3.22
3.22
3.21
3.22
3.30
3.30
3.30
3.29
3.31
75
T.C.
51.3
53.8
54.6
59.3
65.5
53.1
55.1
55.6
60.5
66.2
54.9
56.4
56.6
61.7
66.8
S.C.
34.7
36.7
36.8
40.8
44.6
36.2
37.6
37.7
41.5
45.1
37.6
38.4
38.5
42.2
45.5
KW
3.65
3.69
3.68
3.70
3.72
3.76
3.78
3.78
3.79
3.82
3.86
3.87
3.87
3.88
3.91
85
T.C.
51.3
53.9
54.7
59.8
65.5
53.2
55.2
55.7
60.8
66.5
55.1
56.5
56.7
61.8
67.5
S.C.
35.3
37.3
37.4
41.3
45.3
36.6
38.2
38.2
42.0
45.9
37.9
39.0
39.0
42.8
46.6
KW
4.49
4.52
4.52
4.56
4.60
4.59
4.62
4.62
4.65
4.69
4.69
4.71
4.71
4.75
4.79
95
T.C.
51.3
53.9
54.8
60.2
65.5
53.3
55.3
55.8
61.1
66.9
55.3
56.6
56.7
61.9
68.2
S.C.
35.9
37.9
37.9
41.7
45.9
37.1
38.8
38.7
42.5
46.8
38.2
39.6
39.4
43.3
47.7
KW
5.33
5.36
5.36
5.42
5.47
5.42
5.46
5.46
5.51
5.57
5.52
5.55
5.55
5.61
5.67
105
T.C.
47.6
49.8
50.1
55.5
61.3
49.5
51.0
51.1
56.6
62.7
51.4
52.2
52.1
57.6
64.0
S.C.
34.1
35.6
35.8
39.5
43.3
35.5
36.5
36.5
40.2
44.2
36.8
37.3
37.2
40.8
45.1
KW
5.90
5.94
5.94
6.00
6.08
6.01
6.04
6.03
6.10
6.17
6.12
6.14
6.13
6.20
6.27
115
T.C.
44.2
45.8
46.0
52.1
56.5
45.8
47.1
46.9
53.3
57.7
47.3
48.3
47.7
54.4
58.8
S.C.
31.3
32.8
32.9
36.7
40.4
32.7
33.8
33.6
37.5
41.2
34.0
34.8
34.3
38.3
41.9
KW
6.50
6.52
6.52
6.59
6.68
6.59
6.60
6.61
6.68
6.77
6.68
6.69
6.70
6.77
6.87
125
T.C.
39.5
41.8
41.4
46.7
52.2
41.1
42.9
42.5
47.5
53.1
42.6
44.0
43.6
48.2
53.9
S.C.
28.4
30.1
30.4
33.7
37.4
29.7
31.0
31.0
34.3
38.0
30.9
31.9
31.6
34.8
38.6
KW
7.15
7.21
7.19
7.27
7.34
7.24
7.29
7.28
7.36
7.43
7.34
7.37
7.36
7.45
7.52
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.
COIL MULTIPLIERS - 5 TON
Air Handler
Coil
T.C.
S.C.
KW
AVV61DE42
–
1.00
1.00
1.00